Communications Functions
6-
87
002CH
Inverter
status
Bit
0
Operation
1:
Operating
Bit
1
Zero
speed
1:
Zero speed
Bit
2
Frequency
matching
1:
Matched
Bit
3
User-defined
speed matching
1:
Matched
Bit
4
Frequency
detection 1
1:
Output frequency
≤
L4-01
Bit
5
Frequency
detection 2
Output
frequency
≥
L4-01
Bit
6
Inverter
startup completed
1:
Startup completed
Bit
7
Low
voltage detection 1: Detected
Bit
8
Baseblock
1:
Inverter output baseblock
Bit
9
Frequency
reference mode
1:
Not communications 0: Communications
Bit
A
Run
command mode
1:
Not communications 0: Communications
Bit
B
Overtorque
detection
1:
Detected
Bit
C
Frequency
reference lost
1:
Lost
Bit
D
Retrying
error
1:
Retrying
Bit
E
Error
(including RS-422A/485 communications time-out) 1:Error occurred
Bit
F
Communications
time-out 1: Timed out
002DH
Multi-function
output status
Bit
0
Multi-function
output (terminal M1-M2) 1: ON 0: OFF
Bit
1
Multi-function
output 1 (terminal P1-PC, M3-M4): 1: ON 0: OFF
Bit
2
Multi-function
output 2 (terminal P1-PC, M5-M6): 1: ON 0: OFF
Bits
3 to F
Not
used
002EH
- 0030H Not used
0031H
Main
circuit DC voltage
0032H
- 0037H Not used
0038H
PID
feedback quantity (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H
PID
input quantity (±100%/±Max. output frequency; 10/1%; with sign)
003AH
PID
output quantity (±100%/±Max. output frequency; 10/1%; with sign)
003BH
CPU
software number
003CH
Flash
software number
003DH
Communications
error details
Bit
0
CRC
error
Bit
1
Invalid
data length
Bit
2
Not
used
Bit
3
Parity
error
Bit
4
Overrun
error
Bit
5
Framing
error
Bit
6
Time-out
Bits
7 to F
Not
used
Register
No.
Contents
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...