Terminal
Block
Configuration
2-
9
Control-circuit
Terminals
(Same
for
200-V
and
400-V
Class)
The
functions for the control-circuit terminals by symbol are shown in Table 2.2.
Table
2.2
Control-circuit
Terminal
Functions
Type
Signal
Symbol
Signal
Name
Terminal
Function
Signal
Level
Sequence
Input
S1
Forward-stop
command
Forward
when ON, stop when OFF
+24
VDC, 8 mA
photocoupler
isolation
S2
Reverse-stop
command
Reverse
when ON, stop when OFF
S3
Multi-function
input selection 1
Factory
setting: External fault
detected
when ON
S4
Multi-function
input selection 2
Factory
setting: Fault reset when
ON
S5
Multi-function
input selection 3
Factory
setting: Multi-step speed
command
1 effective when ON
S6
Multi-function
input selection 4
Factory
setting: Multi-step speed
command
2 effective when ON
S7
Multi-function
input selection 5
Factory
setting: Inching frequency
selected
when ON
SC
Sequence
control input common
-
Analog
Input
+V
+15-V
power supply
+15-V
power supply for analog ref-
erence
+15
V (20 mA maximum
allowable
current)
A1
Main
speed frequency reference
0
to 10 V/100%
0
to 10 V (input imped-
ance:
20 k
Ω
)
A2
Multi-function
analog input
4
to 20 mA/100%, 0 to 10 V/100%
Factory
setting: Add to terminal A1
(H3-09
= 0)
4
to 20 mA (input imped-
ance:
20 k
Ω)
0
to 10 V (input imped-
ance:
20 k
Ω
)
AC
Analog
common
0
V
-
E
(G)
Shield
wire, optional ground con-
nection
-
-
Sequence
Output
P1
Multi-function
output 1
Factory
setting: Zero speed
Zero
level (b2-01) or below when
ON.
Open
collector output
+48
VDC, 50 mA
P2
Multi-function
output 2
Factory
setting: Frequency agree-
ment
detection
ON
when the frequency is within
±2 Hz
of the set frequency.
PC
Photocoupler
output common
-
MA
Fault
output (NO contact)
ON
between MA and MC during
fault
ON
between MB and MC during
fault.
Relay
output
Dry
contacts
Contact
capacity
250
VAC, 1 A max.
30
VDC, 1 A max.
MB
Fault
output (NC contact)
MC
Relay
contact output common
-
M1
Multi-function
output (NO con-
tact)
Factory
setting: RUN
ON
between M1 and M2 during
operation.
M2
Analog
Monitor
Output
FM
Multi-function
analog monitor 1
Factory
setting: Output frequency 0
to
10 V/100% frequency
0
to +10 VDC ±5%
2
mA max.
AM
Multi-function
analog monitor 2
Factory
setting: Current monitor 5
V/Inverter
rated current
AC
Analog
common
-
Pulse
Input/Out-
put
RP
Multi-function
pulse input
Factory
setting: Frequency refer-
ence
input (H6-01 = 0)
0
to 32 kHz (3 k
Ω)
MP
Multi-function
pulse monitor
Factory
setting: Output frequency
(H6-06
= 2)
0
to 32 kHz (2.2 k
Ω)