9
-20
n
AC Reactor
An
AC Reactor is used to control harmonics generated by the Inverter or when the power supply capacity is
greatly
larger than the Inverter’s capacity. It is also used to increase the power factor. Select the AC Reactor
from
the following table according to the motor capacity.
Models and Application
The
standard models of AC Reactors are listed in the following table.
Inverter
AC Reactor
Voltage
Class
Max. Appli-
cable Motor
Capacity
(kW)
Model No.
Current
(A)
Inductance
(mH)
Loss
(W)
200-V
Class
0.4
3G3IV-PUZBAB2.5A4.2MH
2.5
4.2
15
0.75
3G3IV-PUZBAB5A2.1MH
5
2.1
15
1.5
3G3IV-PUZBAB10A1.1MH
10
1.1
25
2.2
3G3IV-PUZBAB15A0.7MH
15
0.71
30
3.7
3G3IV-PUZBAB20A0.53MH
20
0.53
35
5.5
3G3IV-PUZBAB30A0.35MH
30
0.35
45
7.5
3G3IV-PUZBAB40A0.265MH
40
0.265
50
11
3G3IV-PUZBAB60A0.18MH
60
0.18
65
15
3G3IV-PUZBAB80A0.13MH
80
0.13
75
18.5
3G3IV-PUZBAB90A0.12MH
90
0.12
90
22
3G3IV-PUZBAB120A0.09MH
120
0.09
90
30
3G3IV-PUZBAB160A0.07MH
160
0.07
100
37
3G3IV-PUZBAB200A0.05MH
200
0.05
110
45
3G3IV-PUZBAB240A0.044MH
240
0.044
125
55
3G3IV-PUZBAB280A0.038MH
280
0.038
130
400-V
Class
0.4
3G3IV-PUZBAB1.3A18.0MH
1.3
18.0
15
0.75
3G3IV-PUZBAB2.5A8.4MH
2.5
8.4
15
1.5
3G3IV-PUZBAB5A4.2MH
5
4.2
25
2.2
3G3IV-PUZBAB7.5A3.6MH
7.5
3.6
35
3.7
3G3IV-PUZBAB10A2.2MH
10
2.2
43
5.5
3G3IV-PUZBAB15A1.42MH
15
1.42
50
7.5
3G3IV-PUZBAB20A1.06MH
20
1.06
50
11
3G3IV-PUZBAB30A0.7MH
30
0.7
65
15
3G3IV-PUZBAB40A0.53MH
40
0.53
90
18.5
3G3IV-PUZBAB50A0.42MH
50
0.42
90
22
3G3IV-PUZBAB60A0.36MH
60
0.36
90
30
3G3IV-PUZBAB80A0.26MH
80
0.26
95
37
3G3IV-PUZBAB90A0.24MH
90
0.24
110
45
3G3IV-PUZBAB120A0.18MH
120
0.18
130
55
3G3IV-PUZBAB150A0.15MH
150
0.15
150
Содержание SYSDRIVE 3G3RV