6
-88
Note Communications
error details are stored until an error reset is input (you can also reset while the Unit is operating). Communications error details can
also
be read by using the register numbers given in the Register column in the U: Monitor parameter table.
Broadcast
Data
The
following table shows the broadcast data. This is write data only.
Note Bit
signals not defined in the broadcast operation signals use local node data signals continuously.
n
ENTER
Command
When
writing parameters to the Inverter from the PLC using RS-422A/485 communications, the parameters
are
temporarily stored in the parameter data area in the Inverter. To enable these parameters in the parameter
data
area, use the ENTER command.
There
are two types of ENTER commands: ENTER commands that enable parameter data in RAM, and
ENTER
commands that write data to EEPROM (non-volatile memory) in the Inverter at the same time as
enabling
data in RAM.
The
following table shows the ENTER command data. ENTER command data can only be written.
The
ENTER command is enabled by writing 0 to register number 0900H or 0901H.
003EH
kVA
setting
003FH
Control
method
Register
Address
Contents
0001H
Operation
signal
Bit
0
Run
command 1: Operating 0: Stopped
Bit
1
Reverse
operation command 1: Reverse 0: Forward
Bits
2 and 3
Not
used
Bit
4
External
error 1: Error (set using H1-01)
Bit
5
Error
reset 1: Reset command (set using H1-02)
Bits
6 to B
Not
used
Bit
C
Multi-function
input S5
Bit
D
Multi-function
input S6
Bit
E
Multi-function
input S7
Bit
F
Not
used.
0002H
Frequency
ref-
erence
30000/100%
Register
No.
Contents
0900H
Write
parameter data to EEPROM
0910H
Parameter
data is not written to EEPROM, but refreshed in RAM only.
INFO
The maximum number of times you can write to EEPROM using the Inverter is 100,000. Do not frequently
execute ENTER commands (0900H) written to EEPROM.
The ENTER command registers are write-only. Consequently, if reading these registers, the register address
will become invalid (Error code: 02H).
Register
No.
Contents