5
-44
n
Communications
Option
Cards:
F6
Parameters
for a Communications Option Card (DeviceNet) are shown in the following table.
Note For
details on Communications Option Cards, refer to the manual for each Option Card (DeviceNet Communications Card/3G3FV-PDRT1-SIN (Cat.
No.
I525-E1)).
* 1. If
F6-01 or F6-03 is set to 3, the Inverter will continue operating. Be sure to install a limit switch or an emergency stop switch as a safety precaution.
* 2. For
(-E) models.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
F6-01
DeviceNet
fault
opera-
tion
selec-
tion
0:
Decelerates to a stop
using
C1-02 deceleration
time/fault
detection
1:
Coast to a stop/fault
detection
2:
Decelerates to stop using
C1-09
deceleration time/
fault
detection
3:
Continues operating/
alarm
detection
*1
0
to 3
1
No
A
A
A
3A2H
-
Comm
Bus
Flt
Sel
F6-02
Communi-
cations
external
fault
input
detection
method
selection
0:
Fault detection during
power
ON
1:
Fault detected during
running
only (when RUN
commands
are input)
0
or 1
0
No
A
A
A
3A3H
-
EF0
Detec-
tion
F6-03
Communi-
cations
external
fault
input
operation
selection
0:
Decelerates to a stop
using
C1-02 deceleration
time/fault
detection
1:
Coast to a stop/fault
detection
2:
Decelerates to a stop
using
C1-09 deceleration
time/fault
detection
3:
Continues operating/
alarm
detection
*1
0
to 3
1
No
A
A
A
3A4H
-
EF0
Fault
Action
F6-04
Not
used
Do
not set.
-
0
No
A
A
A
3A5H
-
Trace
Sam-
ple
Tim
F6-05
Display
unit
selection
for
current
monitor
0:
Amperes
1:
100%/8192
0
or 1
0
No
A
*2
A
*2
A
*2
3A6H
-
Current
Unit
Sel