* The
setting range for acceleration/deceleration times will depends on the setting for C1-10. When C1-10 is set to 0, the setting range for acceleration/decel-
eration
times becomes 0.00 to 600.00 seconds.
C1-09
Decelera-
tion
Stop
Time
The
deceleration time when
the
multi-function input
“Deceleration
stop” is set to
ON.
This
function can be used a
stopped
method when a fault
has
been detected.
0.0
to
6000.0
*
10.0
s
No
A
A
A
208H
6-18
Fast
Stop
Time
C1-10
Accel/decel
time
setting
unit
0: 0.01-second
units
1: 0.1-second
units
0
or 1
1
No
A
A
A
209H
6-19
Acc/Dec
Units
C1-11
Accel/decel
time
switch-
ing
fre-
quency
Sets
the frequency for auto-
matic
acceleration/decelera-
tion
switching.
Below
set frequency: Accel/
decel
time 4
Above
set frequency: Accel/
decel
time 1
The
multi-function input
“accel/decel
time 1” or
“accel/decel
time 2” take pri-
ority.
0.0
to
400.0
0.0
Hz
No
A
A
A
20AH
6-19
Acc/Dec
SW
Freq
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop