Communications Functions
6-
95
m = 100 x Unit No. (Wd)
* Set
to this value.
For
the
SYSMAC
C200HX/HG/HE
and
CQM1H
Series:
Use
the following ports for the SYSMAC C200HX/HG/HE and CQM1H series.
•
C200HW-COM06-V1
Communications Board: Port A
•
CQM1H-SCB41
Serial Communications Board: Port 2
DM
Area
Bit
Setting
Value
Board
Unit
Port
1
Port
2
Port
1
Port
2
D32000
D32010
m
m+10
15
Port
setting -- 0: Default, 1*: Desired setting
14
to 12
Reserved
11
to 08
Serial
communications mode
(6
Hex*: Protocol macro)
07
to 05
Reserved
04
Start
bit -- 0*: 1 bit, 1: 1 bit (fixed at 1 bit regardless of
the
setting)
03
Data
length -- 0: 7 bits, 1*: 8 bits
02
Stop
bit -- 0: 2 bits, 1*: 1 bit
01
Parity
-- 0: With, 1*: Without
00
Parity
-- 0*: Even, 1: Odd
D32001
D32011
m+1
m+11
15
to 04
Reserved
03
to 00
Transmission
rate (unit: bps)
0:
Default (9,600), 3: 1,200, 4: 2,400, 5: 4,800,
6*:
9,600, 7: 19,200, 8: 38,400
-
-
-
-
D32008
D32018
m+8
m+18
15
Transmission
method -- 0: Half-duplex, 1*: Full-
duplex
14
to 00
Reserved
D32009
D32019
m+9
m+19
15
to 00
Max.
number of bytes in send/receive data -- 00C8* to
03E8
Hex
Communications
Board
Bit
Setting
Value
Port
1
Port
A
Port
2
Port
B
DM6555
DM6550
00
to 03
Standard
format setting
0
Hex: Standard setting (default)
1
Hex
*
:
Settings in bits 00 to 15 of DM6656 and DM 6551 are used.
6001
04
to 11
00:
Default
12
to 15
Serial
Communications Board
0
Hex: Host link (default)
1
Hex: Not protocol
2
Hex: 1:1 Link slave
3
Hex: 1:1 Link master
4
Hex: NT link (1:1 mode)
5
Hex: Hex: NT link (1:N mode)
6
Hex
*
:
Protocol macro
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...