Adjusting Frequency References
6-
27
Adjusting
Frequency
References
This
section explains methods of adjusting frequency references.
K
K
K
K
Adjusting
Analog
Frequency
References
Gain
and bias are among the parameters used to adjust analog inputs.
n
Related
Parameters
* For
(-E) models.
n
Adjusting
Analog
Frequency
Reference
Using
Parameters
The
frequency reference is input from the control circuit terminals using analog voltage and current.
If
using frequency reference terminal A1 as an input terminal, perform adjustments using parameters H3-02
and
H3-03. If using multi-function analog input terminal A2 as a frequency reference terminal, perform
adjustments
using H3-10 and H3-11.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
H3-01
Signal
select terminal A1
(voltage)
0:
Voltage limit enabled (Below 0 V is 0 V)
1:
Voltage limit disabled
Set
value 1 can be set for (-E) models.
0
or 1
0
No
A
*
A
*
A
*
Term
A1 Lvl Sel
H3-02
Gain
(terminal A1)
Set
the frequency during 10 V input as a percent,
taking
max. output frequency to be 100%.
0.0
to
1000.0
100.0%
Yes
A
A
A
Terminal
A1 Gain
H3-03
Bias
(terminal A1)
Set
the frequency during 0 V input as a percent,
taking
max. output frequency to be 100%.
-100.0
to
+100.0
0.0%
Yes
A
A
A
Terminal
A1 Bias
H3-08
Multi-function
analog
input
terminal A2 signal
level
selection
0:
Limit negative frequency settings for gain and
bias
settings to 0.
1: Do
not limit negative frequency settings for
gain
and bias settings to 0 (i.e., allow reverse
operation).
2:
4 to 20 mA (9-bit input).
Switch
current and voltage input using the switch
on
the control panel.
0
to 2
2
No
A
A
A
Term
A2 Signal
H3-09
Multi-function
analog
input
terminal A2 function
selection
Select
multi-function analog input function for ter-
minal
A2.
0
to 1F
0
No
A
A
A
Terminal
A2 Sel
H3-10
Gain
(terminal A2)
Set
the reference capacity for each function during
10
V (20 mA) input as a percent.
Set
the 100% content function selected using H3-
09
to 100%.
0.0
to
1000.0
100.0%
Yes
A
A
A
Terminal
A2 Gain
H3-11
Bias
(terminal A2)
Set
the reference capacity for each function during
0
V (4 mA) input as a percent.
Set
the 100% content function selected using H3-
09
to 100%.
-100.0
to
+100.0
0.0%
Yes
A
A
A
Terminal
A2 Bias