6
-134
When
E1-03 is set to F (User-defined V/f pattern), you can set parameters E1-04 to E1-10. If E1-03 is set to
anything
other than F, you can only refer to parameters E1-04 to E1-10. If the V/f characteristics are linear, set
E1-07
and E1-09 to the same value. In this case, E1-08 will be ignored.
Fig 6.79 User-Set V/f Pattern
n
Setting
Precautions
When
the setting is to user-defined V/f pattern, beware of the following points.
•
When
changing control method, parameters E1-07 to E1-10 will change to the factory settings for that
control
method.
•
Be
sure to set the four frequencies as follows:
E1-04
(FMAX)
≥
E1-06 (FA)
>
E1-07 (FB)
≥
E1-09 (FMIN)
Output voltage (V)
E1-05
(VMAX)
E1-13
(V Base)
E1-08
(VC)
E1-10
(VMIN)
E1-09
(FMIN)
E1-07
(FB)
E1-06
(FA)
E1-04
(FMAX)
Frequency (Hz)