Parameter Tables
5-
21
n
S-curve
Acceleration/Deceleration:
C2
Parameters
for S-curve characteristics are shown in the following table.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
C2-01
S-curve
character-
istic
time
at
acceler-
ation
start
All
sections of the S-curve charac-
teristic
time are set in seconds.
When
the S-curve characteristic
time
is set, the accel/decel times will
increase
by only half of the S-curve
characteristic
times at start and end.
0.00
to
2.50
0.20
s
No
A
A
A
20BH
6-20
SCrv
Acc
@
Start
C2-02
S-curve
character-
istic
time
at
acceler-
ation
end
0.00
to
2.50
0.20
s
No
A
A
A
20CH
6-20
SCrv
Acc
@
End
C2-03
S-curve
character-
istic
time
at
deceler-
ation
start
0.00
to
2.50
0.20
s
No
A
A
A
20DH
6-20
SCrv
Dec
@
Start
C2-04
S-curve
character-
istic
time
at
deceler-
ation
end
0.00
to
2.50
0.00
s
No
A
A
A
20EH
6-20
SCrv
Dec
@
End
Run command
Output frequency
Time
ON
OFF
C2-02
C2-03
C2-04
C2-01
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...