Individual Functions
6-
119
* The
parameters b5-18 and b5-19 are enabled only with (-E) models.
Multi-Function
Digital
Inputs
(H1-01
to
H1-05)
Multi-Function
Analog
Input
(H3-09)
b5-16
PID
sleep operation delay
time
Set
the delay time until the PID sleep function
starts
in seconds.
0.0
to
25.5
0.0
s
No
A
A
A
PID
Sleep Time
b5-17
Accel/decel
time for PID
reference
Set
the accel/decel time for PID reference in sec-
onds.
0.0
to
25.5
0.0
s
No
A
A
A
PID
Acc/Dec Time
b5-18
PID
set point selection
0:
PID set point disabled
1:
PID set point enabled
0
or 1
0
No
A
*
A
*
A
*
PID
Setpoint Sel
b5-19
PID
set point
PID
set point
0.0
to
100.0
0.0%
No
A
*
A
*
A
*
PID
Setpoint
H6-01
Pulse
train input function
selection
0:
Frequency reference
1:
PID feedback value
2:
PID target value
0
to 2
0
No
A
A
A
Pulse
Input Sel
Param-
eter
Num-
ber
Name
Description
Output
Signal
Level
During
Multi-Function
Analog
Output
Min.
Unit
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
U1-24
PID
feedback value
Monitors
the feedback value when
PID
control is used.
The
input for the max. frequency cor-
responds
to 100%.
10
V: Max. frequency (0 to ± 10 V
possible)
0.01%
A
A
A
PID
Feedback
U1-36
PID
input volume
PID
feedback volume
Given
as maximum frequency/100%
10
V: Max. frequency (0 to ± 10 V
possible)
0.01%
A
A
A
PID
Input
U1-37
PID
output volume
PID
control output
Given
as maximum frequency/100%
10
V: Max. frequency (0 to ± 10 V
possible)
0.01%
A
A
A
PID
Output
U1-38
PID
command
PID
c PID command bias
Given
as maximum frequency/100%
10
V: Max. frequency
0.01%
A
A
A
PID
Setpoint
Set
Value
Function
Control
Methods
V/f
V/f
with
PG
Open
loop
Vec-
tor
19
PID
control disable (ON: PID control disabled)
Yes
Yes
Yes
30
PID
control integral reset (reset when reset command is input or when stopped during PID control)
Yes
Yes
Yes
31
PID
control integral hold (ON: Integral hold)
Yes
Yes
Yes
34
PID
soft starter
Yes
Yes
Yes
35
PID
input characteristics switch
Yes
Yes
Yes
Set
Value
Function
Control
Methods
V/f
V/f
with
PG
Open
loop
Vec-
tor
B
PID
feedback
Max.
output frequency
Yes
Yes
Yes
C
PID
target value
Max.
output frequency
Yes
Yes
Yes
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display