6
-74
10
V/100% monitor output
×
output
gain + output bias
Fig 6.53 Monitor Output Adjustment
n
Switching
Analog
Monitor
Signal
Levels
Monitor
items corresponding to 0 to ±10 V output 0 to 10 V signals when the monitor value is positive (+),
and
0 to -10 V signals when the monitor value is negative (-). For monitor items corresponding to 0 to ±10 V,
refer
to Chapter 5 Parameters.
K
K
K
K
Using
Pulse
Train
Monitor
Parameters
This
section explains pulse monitor parameters.
n
Related
Parameters
n
Selecting
Pulse
Monitor
Items
Output
digital operator monitor items (U1-
oo
[status monitor]) from pulse monitor terminal MP-SC. Refer to
Chapter
5 Parameters, and set the
oo
part of U1-
oo
(Status monitor). The possible monitor selections are
limited
as follows: U1-01, 02, 05, 20, 24, 36.
INFO
You can select the signal levels separately for multi-function analog output terminals and analog output option
terminals.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
H6-06
Pulse
train monitor selec-
tion
Select
the pulse train monitor output items (value
of
the
oo
part of U1-
oo
).
There
are two types of monitor items: Speed-
related
items and PID-related items.
1,
2, 5,
20,
24, 36
2
Yes
A
A
A
Pulse
Moni Sel
H6-07
Pulse
train monitor scaling Set the number of pulses output when speed is
100%
in hertz.
Set
H6-06 to 2, and H6-07 to 0, to make the pulse
train
monitor output synchronously to the output
frequency.
0
to
32000
1440
Hz
Yes
A
A
A
Pulse
Moni Scale
Output voltage
Gain x 10 V
Bias x 10/100 V
Monitor item
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...