6
-70
K
K
K
K
Switching
Operations
between
a
Communications
Option
Card
and
Con-
trol
Circuit
Terminals
You
can switch reference input between the Communications Option Card and the control circuit terminals.
Set
one of the parameters H1-01 to H1-05 (multi-function input terminal S3 to S7 function selection) to 2
(Option/Inverter
selection) to enable switching reference input using the terminal ON/OFF status when the
Inverter
is stopped.
n
Setting
Precautions
To
switch command inputs between the Communications Option Card and the control circuit terminals, set the
following
parameters.
•
Set
b1-01 (Reference Selection) to 1 (Control circuit terminal [analog input])
•
Set
b1-02 (Operation Method Selection to 1 (Control circuit terminal (sequence inputs])
•
Set
one of the parameters H1-01 to H1-05 (multi-function contact input terminal S3 to S7 function selec-
tion)
to 2 (Option/Inverter selection).
K
K
K
K
Jog
Frequency
Operation
without
Forward
and
Reverse
Commands
(FJOG/RJOG)
The
FJOG/RJOG command functions operate the Inverter using jog frequencies by using the terminal ON/
OFF
operation. When using the FJOG/RJOG commands, there is no need to input the run command.
To
use this function, set one of the parameters H1-01 to H1-05 (multi-function contact input terminal S3 to S7
function
selection) to 12 (FJOG command) or 13 (RJOG command).
n
Related
Parameters
Multi-Function
Digital
Inputs
(H1-01
to
H1-05)
Terminal
Status
Frequency
Reference
and
Run
Command
Selection
OFF
Inverter
(Can
be operated from frequency reference or control circuit terminal from analog input termi-
nal.)
ON
Communications
Option Card
(Frequency
reference and run command are enabled from communications Option Card.)
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
d1-17
Jog
frequency reference
The
frequency reference when the jog frequency
reference
selection, FJOG command, or RJOG
command
is ON.
0
to
400.00
6.00
Hz
Yes
Q
Q
Q
Jog
Reference
Set
Value
Function
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
12
FJOG
command (ON: Forward run at jog frequency d1-17)
Yes
Yes
Yes
13
RJOG
command (ON: Reverse run at jog frequency d1-17)
Yes
Yes
Yes