Parameter Tables
5-
73
n
Copy
Function:
o3
Parameters
for the copy function are shown in the following table.
K
K
K
K
T:
Motor
Autotuning
The
following settings are made with the motor autotuning parameters (T parameters): Settings for autotuning.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
o3-01
Copy
func-
tion
selec-
tion
0:
Normal operation
1:
READ (Inverter to
Operator)
2:
COPY (Operator to
Inverter)
3:
Verify (compare)
0
to 3
0
No
A
A
A
515H
6-137
Copy
Func
Select
o3-02
Read
per-
mitted
selection
0:
Read prohibited
1:
Read permitted
0
or 1
0
No
A
A
A
516H
6-137
Copy
Allowable
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
T1-00
Motor
1/2
selection
Set
the location where the
autotuned
motor constants
are
to be stored.
1:
E1 to E2 (motor 1)
2:
E3 to E4 (motor 2)
1
or 2
1
No
No
No
A
700H
4-13
Select
Motor
T1-01
Autotuning
mode
selec-
tion
Set
the autotuning mode.
0:
Rotational autotuning
1:
Stationary autotuning
2:
Stationary autotuning for
line-to-line
resistance
only
0
to 2
*1
0
No
A
A
A
701H
4-11
4-13
Tuning
Mode
Sel
T1-02
Motor
out-
put
power
Set
the output power of the
motor
in kilowatts.
0.00
to
650.00
0.40
kW
No
A
A
A
702H
4-13
Mtr
Rated
Power
T1-03
Motor
rated
voltage
Set
the rated voltage of the
motor
in volts.
0
to
255.0
*2
200.0
V
*2
No
No
No
A
703H
4-13
Rated
Volt-
age