Individual Functions
6-
129
K
K
K
K
Setting
the
V/f
Pattern
In
V/f control method, you can set the Inverter input voltage and the V/f pattern as the need arises.
n
Related
Parameters
* 1. These
are values for a 200-V Class Inverter. Values for a 400-V Class Inverter are double.
* 2. The
factory setting will change when the control method is changed. (V/f control factory settings are given.)
* 3. The
contents of parameters E1-11 and E1-12 are ignored when set to 0.00.
* 4. E1-13
is set to the same value as E1-05 by autotuning.
* 5. When
C6-01 is set to 0, the upper limit of the setting range is 150.0 Hz.
* 6. For
(-E) models. Factory setting for base frequency is 50 Hz.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
E1-01
Input
voltage setting
Set
the Inverter input voltage in 1 volt. This setting
is
used as a reference value in protection func-
tions.
155
to
255
*1
200
V
*1
No
Q
Q
Q
Input
Voltage
E1-03
V/f
pattern selection
0
to E: Select from the 15 preset V/f patterns.
F:
Custom
user-set patterns (Application for
settings
E1-04 to E1-10.)
0
to F
F
No
Q
Q
No
V/F
Selection
E1-04
Max.
output frequency
(FMAX)
To
set V/f characteristics in a straight line, set the
same
values for E1-07 and E1-09. In this case, the
setting
for E1-08 will be disregarded.
Always
ensure that the four frequencies are set in
the
following manner:
E1-04
(FMAX)
≥
E1-06 (FA)
>
E1-07
(FB)
≥
E1-09 (FMIN)
40.0
to
400.0
*5
60.0
Hz
(50.00
Hz)*6
No
Q
Q
Q
Max
Frequency
E1-05
Max.
voltage (VMAX)
0.0
to
255.0
*1
200.0
V
*1
*2
No
Q
Q
Q
Max
Voltage
E1-06
Base
frequency (FA)
0.0
to
400.0
60.0
Hz
(50.00
Hz)*6
No
Q
Q
Q
Base
Frequency
E1-07
Mid.
output frequency
0.0
to
400.0
3.0
Hz
*2
No
A
A
A
Mid
Frequency A
E1-08
Mid.
output frequency
voltage
0.0
to
255.0
15.0
V
*1
*2
No
A
A
A
Mid
Voltage A
E1-09
Min.
output frequency
(FMIN)
0.0
to
400.0
1.5
Hz
*2
No
Q
Q
Q
Min
Frequency
E1-10
Min.
output frequency
voltage
0.0
to
255.0
*1
9.0
V
*1
*2
No
A
A
A
Min
Voltage
E1-11
Mid.
output frequency 2
Set
only to fine-adjust V/f for the output range.
Normally,
this setting is not required.
0.0
to
400.0
0.0
Hz
*3
No
A
A
A
Mid
Frequency B
E1-12
Mid.
output frequency
voltage
2
0.0
to
255.0
*1
0.0
V
*3
No
A
A
A
Mid
Voltage B
E1-13
Base
voltage
0.0
to
255.0
*1
0.0
V
*4
No
A
A
Q
Base
Voltage
Output voltage (V)
Frequency (Hz)
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...