Run Command
6-
13
Performing
Operations
Using
a
3-wire
Sequence
By
selecting 0 for any parameter from H1-01 to H1-05 (related to terminals S3 to S7), the selected terminal
functions
as a forward/reverse run command, and terminals S1 and S3 change functions to 3-wire sequence
commands.
When
the Inverter is initialized for 3-wire sequence control (A1-03=3330), multi-function input 3 (terminal
S5)
will be the forward/reverse direction.
Fig 6.13 3-wire Sequence Wiring Example
Fig 6.14 Three-wire Sequence Time Chart
INFO
Use a sequence that turns ON terminal S1 for 50 ms or longer for the run command. This will make the run
command self-holding in the Inverter.
Stop switch
(NC contact)
Operation switch
(NO contact)
Run command
(operates when ON)
Stop command
(stopped when OFF)
Forward/reverse direction
(multi-function input)
Sequence input common
50 ms min.
Run command
Forward/reverse
direction
Motor speed
Can be either ON or OFF
OFF
(stopped)
OFF (forward)
ON (reverse)
Stop
Forward
Reverse
Stop
Forward
Stop command
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...