5
-52
n
Multi-function
Analog
Outputs:
H4
Parameters
for multi-function analog outputs are shown in the following table.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
H4-01
Monitor
selection
(terminal
FM)
Sets
the number of the moni-
tor
item to be output (U1-
@@
)
from terminal FM.
4,
10 to 14, 28, 34, 39, 40
cannot
be set. 17, 23, 25, 29,
30,
31, 35 are not used.
1
to 40
2
No
A
A
A
41DH
6-72
Terminal
FM
Sel
H4-02
Gain
(termi-
nal
FM)
Sets
the multi-function ana-
log
output 1 voltage level
gain.
Sets
whether the monitor
item
output will be output in
multiples
of 10 V.
The
maximum output from
the
terminal is 10 V.
0.00
to
2.50
(0.0
to
1000.0)
*
1.00
(100.0%)
*
Yes
Q
Q
Q
41EH
4-8
6-72
Terminal
FM
Gain
H4-03
Bias
(termi-
nal
FM)
Sets
the multi-function ana-
log
output 1 voltage level
bias.
Sets
output characteristic up/
down
parallel movement as a
percentage
of 10 V.
The
maximum output from
the
terminal is 10 V.
-10.0
to
+10.0
(-110.0
to
+110.0)
*
0.0%
Yes
A
A
A
41FH
4-8
Terminal
FM
Bias
H4-04
Monitor
selection
(terminal
AM)
Sets
the number of the moni-
tor
item to be output (U1-
@@
)
from terminal AM.
4,
10 to 14, 28, 34, 39, 40
cannot
be set. 17, 23, 25, 29,
30,
31, 35 are not used.
1
to 40
3
No
A
A
A
420H
4-8
6-72
Terminal
AM
Sel
H4-05
Gain
(termi-
nal
AM)
Set
the voltage level gain for
multi-function
analog out-
put
2.
Set
the number of multiples
of
10 V to be output as the
100%
output for the monitor
items.
The maximum output
from
the terminal is 10 V.
0.00
to
2.50
(0.0
to
1000.0)
*
0.50
(50.0%)
*
Yes
Q
Q
Q
421H
4-8
6-72
Terminal
AM
Gain
H4-06
Bias
(termi-
nal
AM)
Sets
the multi-function ana-
log
output 2 voltage level
bias.
Sets
output characteristic up/
down
parallel movement as a
percentage
of 10 V.
The
maximum output from
the
terminal is 10 V.
-10.0
to
+10.0
(-110.0
to
+110.0)
*
0.0%
Yes
A
A
A
422H
6-72
Terminal
AM
Bias
H4-07
Analog
out-
put
1 signal
level
selec-
tion
Sets
the signal output level
for
multi-function output 1
(terminal
FM)
0: 0
to +10 V output
1: 0
to ±10 V output
(2:
4 to 20 mA)
*
0
or 1
(0
to 2)
*
0
No
A
A
A
423H
6-72
AO
Level
Select1
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...