Trial Operation Procedures
4-
7
K
K
K
K
Basic
Settings
Switch
to the quick programming mode (the QUICK indicator on the Digital Operation should be lit) and then
set
the following parameters. Refer to Chapter 3 Digital Operator and Modes for Digital Operator operating
procedures
and to Chapter 5 Parameters and Chapter 6 Parameter Settings by Function for details on the
parameters.
Parameters
that must be set are listed in Table 4.2 and those that are set according to the application are listed
in
Table 4.3.
Table 4.2 Parameters that must be set
Parame-
ter Num-
ber
Name
Description
Setting Range
Factory
Setting
Page
A1-02
Control
method
selection
Set
the control method for the Inverter.
0:
V/f control
1:
V/f control with PG
(Pulse
generator as encoder)
2:
Open-loop vector control
0
to 2
0
5-9
b1-01
Reference
selection
Set
the frequency reference input method.
0:
Digital Operator
1:
Control circuit terminal (analog input)
2:
RS-422A/485 communications
3:
Option Card
4:
Pulse train input
0
to 4
1
5-11
6-6
6-62
6-76
b1-02
Operation
method
selection
Set
the run command input method.
0:
Digital Operator
1:
Control circuit terminal (sequence input)
2:
RS-422A/485 communications
3:
Option Card
0
to 3
1
5-12
6-12
6-62
6-76
C1-01
Acceleration
time 1
Set
the acceleration time in seconds for the
output
frequency to climb from 0% to 100%.
0.0
to 6000.0
10.0
s
5-19
6-19
C1-02
Deceleration
time 1
Set
the deceleration time in seconds for the
output
frequency to fall from 100% to 0%.
0.0
to 6000.0
10.0
s
5-19
6-19
C6-01
CT/VT
selection
Set
to CT (not low noise, maximum current
overload:
150%) or VT (low noise, maxi-
mum
current overload:120%).
0:
CT
1:
VT
0
or 1
1
5-25
6-2
E1-01
Input
voltage set-
ting
Set
the Inverter's nominal input voltage in
volts.
155
to 255 V
(200
V class)
310
to 510 V
(400
V class)
200
V
(200
V
class)
400
V
(400
V
class)
5-31
6-129
E2-01
Motor
rated current Set the motor rated current.
10%
to 200% of
Inverter's
rated
current
Setting
for
general-
purpose
motor
of
same
capacity
as
Inverter
5-33
6-47
6-127