The
communications processing times for the Inverter are as follows.
•
Inverter
communications input scan: 8 ms
•
Inverter
communications output scan: 8 ms
•
Internal
processing time for the Inverter: Approx. 20 ms
The
I/O response times for the Inverter are illustrated in the following diagram.
Fig 6.73 I/O Response Time
Ladder program cycle time
Communications time x 2
Inverter I/O scan
Internal processing for
the Inverter
Max. input
Max. output