Communications Functions
6-
101
n
Creating
a
Project
File
The
following descripton provides information about how to create a project file to send the RUN command
and
frequency references to three Inverters and read the Inverter status. (“PST” indicates the WS01-PSTF1-J
Protocol
Support Tool.)
First,
select from I/O items, monitor items, and parameters the data to be exchanged according to the applica-
tion.
Then consider what sequence is required by using the protocol macro function.
Example:
Writes control input items (such as the RUN command and multi-function input) of the Inverter and
frequency
reference, monitors the control output (such as error output and RUN output) of the Inverter, and
monitors
the Inverter status.
Three
Inverters with Slave addresses from 01 to 03 are installed for communications.
Checking
the
Register
Numbers
In
the above example, the following three registers are required.
Control
Input: Register 0001 Hex for RUN command
Frequency
Reference: Register 0002 Hex
Control
Output: Register 002C Hex for Inverter status
Memory
Allocations
The
PMCR instruction sends each Slave the data in consecutive words specified by the operand and beginning
with
the first word (S), and writes in the memory area beginning with the first word (D) the data received.
The
following memory allocations are made in the above example.
SYSMAC CS or CJ-series Programmable Controllers
PMCR
SYSDRIVE
3G3RV
S
D
Communications
Board/Unit
Protocol macro function
Word
Data
S
S
1
S
2
S
3
S
4
S
5
S
6
S
7
S
8
S
9
S
10
D
D
1
D
2
D
3
No. of Slaves 0003
First Slave address 0001
RUN command to Slave 1
Frequency reference to Slave 1
Second Slave address 0002
RUN command to Slave 2
Frequency reference to Slave 2
Third Slave address 0003
RUN command to Slave 3
Frequency reference to Slave 3
Slave 1 Inverter status
Slave 2 Inverter status
Slave 3 Inverter status
RS-422A
/485
C1
C2
Sequence No.
0000 to 03E7 Hex 000
999
Control data
Communica-
tions port
0 to 7 Hex
C1
C2
Serial port
Port 1: 1 Hex
Port 2: 2 Hex
Communications Board/Unit
number designation
Inner Board: E1 Hex
CPU Bus Unit: Unit No.
10 Hex
Number of
data items sent in accordance with
PMCR instruction 000B
Number of data items received in accordance with
PMCR instruction 0003