5
-46
5
Multi-step
speed reference 3
Yes
Yes
Yes
6-10
6
Jog
frequency command (higher priority than multi-step speed reference)
Yes
Yes
Yes
6-10
7
Accel/decel
time 1
Yes
Yes
Yes
6-20
8
External
baseblock NO (NO contact: Baseblock at ON)
Yes
Yes
Yes
6-63
9
External
baseblock NC (NC contact: Baseblock at OFF)
Yes
Yes
Yes
6-63
A
Acceleration/deceleration
ramp hold (ON: Acceleration/deceleration stopped, fre-
quency
on hold)
Yes
Yes
Yes
6-64
B
OH2
alarm signal input (ON: OH2 will be displayed)
Yes
Yes
Yes
-
C
Multi-function
analog input selection (ON: Enable)
Yes
Yes
Yes
-
D
No
V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
trol)
No
Yes
No
-
E
Speed
control integral reset (ON: Integral control disabled)
No
Yes
No
-
F
Not
used (Set when a terminal is not used)
-
-
-
-
10
Up
command (Always set with the down command)
Yes
Yes
Yes
6-65
11
Down
command (Always set with the up command)
Yes
Yes
Yes
6-65
12
FJOG
command (ON: Forward run at jog frequency d1-17)
Yes
Yes
Yes
6-70
13
RJOG
command (ON: Reverse run at jog frequency d1-17)
Yes
Yes
Yes
6-70
14
Fault
reset (Reset when turned ON)
Yes
Yes
Yes
7-2
15
Deceleration
stop. (Normally open condition: Deceleration to stop in deceleration
time
set in C1-09 when ON.)
Yes
Yes
Yes
6-18
16
Motor
switch command (Motor 2 selection)
Yes
Yes
Yes
-
17
Deceleration
stop (Normally closed condition: Deceleration to stop in deceleration
time
set in C1-09 when OFF)
Yes
Yes
Yes
6-18
18
Timer
function input (Functions are set in b4-01 and b4-02 and the timer function
outputs
are set in H1-
oo
and H2-
oo
.)
Yes
Yes
Yes
6-
116
19
PID
control disable (ON: PID control disabled)
Yes
Yes
Yes
6-
120
1A
Accel/Decel
time 2
Yes
Yes
Yes
6-20
1B
Parameters
write enable (ON: All parameters can be written-in. OFF: All parame-
ters
other than frequency monitor are write protected.)
Yes
Yes
Yes
6-141
1C
Trim
control increase (ON: d4-02 frequency is added to analog frequency refer-
ence.)
Yes
Yes
Yes
6-68
1D
Trim
control decrease (ON: d4-02 frequency is subtracted from analog frequency
reference.)
Yes
Yes
Yes
6-68
1E
Analog
frequency reference sample/hold
Yes
Yes
Yes
6-69
20
to
2F
External
fault (Desired settings possible)
Input
mode: NO contact/NC contact, Detection mode: Normal/during operation
Yes
Yes
Yes
6-71
30
PID
control integral reset (reset when reset command is input or when stopped dur-
ing
PID control)
Yes
Yes
Yes
6-
120
31
PID
control integral hold (ON: Hold)
Yes
Yes
Yes
6-
120
32
Multi-step
speed command 4
Yes
Yes
Yes
-
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...