4
-4
Trial
Operation
Procedures
The
procedure for trial operation is described in order in this section.
K
K
K
K
Application
Confirmation
First,
confirm the application before using the Inverter.
•
Fan,
blower, pump
•
Other
equipment
For
any Inverter application other than a fan, blower, or pump, set C6-01 (CT/VT Selection) to 0 (CT: low car-
rier,
fixed torque). The default setting is 1 (VT: high carrier, variable torque).
K
K
K
K
Setting
the
Power
Supply
Voltage
Jumper
(400-V
Class
Inverters
of
75
kW
or
Higher)
For
400-V class Inverters of 75 kW or higher, the power supply terminal for the external fan and internal con-
tact
is separated from the main circuit.
Set
the power supply voltage jumper after setting E1-01 (Input Voltage Setting). Insert the jumper into the
voltage
connector nearest to the actual power supply voltage.
The
jumper is factory-set to 440 V when shipped. If the power supply voltage is not 440 V, use the
following
procedure to change the setting.
1. Turn
OFF the power supply and wait for at least 5 minutes.
2. Confirm
that the CHARGE indicator has gone out.
3. Remove
the terminal cover.
4. Insert
the jumper at the position for the voltage supplied to the Inverter (see Fig 4.2).
5. Return
the terminal cover to its original position.
Fig 4.2 Large-capacity Inverter Connections
Power tab
Jumper (factory-set position)
CHARGE indicator
200 V class power supply
400V class power supply
Power supply input terminals