6
-144
* The
factory setting for (-E) models is 1024.
n
Using
PG
Speed
Control
Card
There
are four types of PG Speed Control Card that can be used in V/f control with PG.
•
3G3FV-PPGA2:
A-phase (single) pulse input, compatible with open collector or complimentary outputs.
•
3G3FV-PPGB2:
A/B-phase pulse input, compatible with complimentary outputs.
•
3G3FV-PPGD2:
A-phase (single) pulse input, compatible with line drivers.
•
3G3FV-PPGX2:
A/B/Z-phase pulse input, compatible with line drivers.
For
the connection diagram, refer to page 2-50.
n
Setting
Number
of
PG
Pulses
Set
the number of PG (Pulse Generator/Encoder) pulses in pulses/rotation. Set the number of A-phase or B-
phase
pulses per 1 motor rotation in F1-01.
n
Matching
PG
Rotation
Direction
and
Motor
Rotation
Direction
Parameter
F1-05 matches the PG rotation direction and the motor rotation direction. If the motor is rotating
forwards,
set whether it is A-phase driven or B-phase driven. Make this setting when using 3G3FV-PPGB2 or
3G3FV-PPGX2.
F1-08
Overspeed
(OS) detection
level
Sets
the overspeed detection method.
Frequencies
above that set for F1-08 (set as a per-
centage
of the maximum output frequency) that
continue
to exceed this frequency for the time set
in
F1-09 are detected as overspeed faults.
0
to 120
115%
No
No
A
No
PG
Overspd Level
F1-09
Overspeed
detection delay
time
(OS)
0.0
to 2.0
1.0
s
No
No
A
No
PG
Overspd Time
F1-10
Excessive
speed deviation
(DEV)
detection level
Sets
the speed deviation detection method.
Any
speed deviation above the F1-10 set level
(set
as a percentage of the maximum output fre-
quency)
that continues for the time set in F1-11 is
detected
as a speed deviation.
Speed
deviation is the difference between actual
motor
speed and the reference command speed.
0
to 50
10%
No
No
A
No
PG
Deviate Level
F1-11
Excessive
speed deviation
detection
delay time
(DEV)
0.0
to
10.0
0.5
s
No
No
A
No
PG
Deviate Time
F1-12
Number
of PG gear teeth 1
Sets
the number of teeth on the gears if there are
gears
between the PG and the motor.
A
gear ratio of 1 will be used if either of these
parameters
is set to 0.
0
to 1000
0
No
No
A
No
PG#
Gear Teeth1
F1-13
Number
of PG gear teeth 2
0
No
No
A
No
PG#
Gear Teeth2
F1-14
PG
open-circuit detection
time
Used
to set the PG disconnection detection time.
PGO
will be detected if the detection time contin-
ues
beyond the set time.
0.0
to
10.0
2.0
s
No
No
A
No
PGO
Detect Time
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
Input pulses input from PG 60
F1-13
F1-01
F1-12
Содержание SYSDRIVE 3G3RV