5
-14
* The
factory setting will change when the control method is changed. (V/f control factory settings are given.)
n
Timer
Function:
b4
Parameters
for timer functions are shown in the following table.
* For
(-E) models.
b3-03
Speed
search
decelera-
tion
time
(current
detection)
Sets
the output frequency
deceleration
time during speed
search
in 1-second units.
Set
the time for deceleration
from
the maximum output fre-
quency
to the minimum out-
put
frequency.
0.1
to
10.0
2.0
s
No
A
No
A
193H
6-53
SpdSrch
Dec
Time
b3-05
Speed
search
wait
time
(cur-
rent
detec-
tion
or
speed
cal-
culation)
Sets
the contactor operating
delay
time when there is a con-
tactor
on the output side of the
Inverter.
When a speed search
is
performed after recovering
from
a momentary power loss,
the
search operation is delayed
by
the time set here.
0.0
to
20.0
0.2
s
No
A
A
A
195H
6-53
Search
Delay
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
V/f
V/f
with
PG
Open
Loop
LCD
Display
b4-01
Timer
func-
tion
ON-
delay
time
Sets
the timer function out-
put
ON-delay time (dead
band)
for the timer function
input,
in 1-second units.
Enabled
when a timer func-
tion
is set in H1-
oo
or H2-
oo
.
0.0
to
300.0
(0.0
to
3000.0)
*
0.0
s
No
A
A
A
1A3H
6-116
Delay-ON
Timer
b4-02
Timer
func-
tion
OFF-
delay
time
Sets
the timer function out-
put
OFF-delay time (dead
band)
for the timer function
input,
in 1-second units.
Enabled
when a timer func-
tion
is set in H1-
oo
or H2-
oo
0.0
to
300.0
(0.0
to
3000.0)
*
0.0
s
No
A
A
A
1A4H
6-116
Delay-OFF
Timer
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Regis-
ter
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...