Parameter Tables
5-
65
n
Torque
Limits:
L7
Parameters
for torque limits are shown in the following table.
n
Hardware
Protection:
L8
Parameters
for hardware protection functions are shown in the following table.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
L7-01
Forward
drive
torque
limit
Sets
the torque limit value as a per-
centage
of the motor rated torque.
Four
individual regions can be set.
0
to
300
200%
No
No
No
A
4A7H
6-40
Torq
Limit
Fwd
L7-02
Reverse
drive
torque
limit
0
to
300
200%
No
No
No
A
4A8H
6-40
Torq
Limit
Rev
L7-03
Forward
regenera-
tive
torque
limit
0
to
300
200%
No
No
No
A
4A9H
6-40
Torq
Lmt
Fwd
Rgn
L7-04
Reverse
regenera-
tive
torque
limit
0
to
300
200%
No
No
No
A
4AAH
6-40
Torq
Lmt
Rev
Rgn
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
L8-01
Protect
selection
for
internal
DB
resistor
0: Disabled
(no overheating
protection)
1: Enabled
(overheating
protection)
0
or 1
0
No
A
A
A
4ADH
6-60
DB
Resis-
tor
Prot
L8-02
Overheat
pre-alarm
level
Sets
the detection tempera-
ture
for the Inverter overheat
detection
pre-alarm in
°
C.
The
pre-alarm detects when
the
cooling fin temperature
reaches
the set value.
50
to
130
95
°
C*
No
A
A
A
4AEH
6-61
OH
Pre-
Alarm
Lvl
Output torque
Positive torque
Reverse
Negative torque
No. of
motor
rotations
Regenerative
state
Regenerative
state
Forward
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...