Parameter Tables
5-
17
* The
parameters b5-18 and b5-19 are enabled only with (-E) models.
n
Dwell
Functions:
b6
Parameters
for dwell functions are shown in the following table.
b5-17
Accel/decel
time
for PID
reference
Set
the accel/decel time for
PID
reference in seconds.
0.0
to
25.5
0.0
s
No
A
A
A
1B5H
6-118
PID
Acc/
Dec
Time
b5-18
PID
set
point
selec-
tion
0:
PID set point disabled
1:
PID set point enabled
0
or 1
0
No
A*
A*
A*
1DCH
6-118
PID
Set-
point
Sel
b5-19
PID
set
point
PID
set point
0.0
to
100.0
0.0%
No
A*
A*
A*
1DDH
6-118
PID
Set-
point
Param
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
b6-01
Dwell
fre-
quency
at
start
The dwell function is used to output
frequency temporarily when driving a
motor with a heavy load.
0.0
to
400.0
0.0
Hz
No
A
A
A
1B6H
6-22
Dwell
Ref
@Start
b6-02
Dwell
time
at
start
0.0
to
10.0
0.0
s
No
A
A
A
1B7H
6-22
Dwell
Time@
Start
b6-03
Dwell
fre-
quency
at
stop
0.0
to
400.0
0.0
Hz
No
A
A
A
1B8H
6-22
Dwell
Ref
@Stop
b6-04
Dwell
time
at
stop
0.0
to
10.0
0.0
s
No
A
A
A
1B9H
6-22
Dwell
Time
@Stop
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
Run command
Output frequency
Time
ON
b6-03
OFF
b6-01
b6-04
b6-02