Parameter Tables
5-
89
Note Attach
a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200-V class
Inverters
with outputs of 0.4 to 11 kW.
* If
C6-02 is set to 0, 1, or F and the initial value of C6-03 and C6-04 is 2.0 kHz, the initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4:
10 kHz,
5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 7.5 kW or more, the Inverter
rated
current will need to be reduced.
Parame-
ter
Num-
ber
Name
Unit
Factory Setting
-
Inverter Capacity
kW
160
185
220
300
o2-04
kVA selection
-
34
35
36
37
b8-03
Energy-saving
filter time
constant
s
2.00
(Open loop vector con-
trol)
b8-04
Energy-saving
coeffi-
cient
-
30.13
30.57
27.13
21.76
C6-02
Carrier
frequency selec-
tion
*
-
3
3
1
1
-
Carrier
frequency selec-
tion
upper limit
-
4
4
1
1
E2-01
(E4-01)
Motor
rated current
A
270.0
310.0
370.0
500.0
E2-02
(E4-02)
Motor
rated slip
Hz
1.35
1.30
1.30
1.25
E2-03
(E4-03)
Motor
no-load current
A
70.0
81.0
96.0
130.0
E2-05
(E4-05)
Motor
line-to-line resis-
tance
Ω
0.029
0.025
0.020
0.014
E2-06
(E4-06)
Motor
leak inductance
%
20.0
20.0
20.0
20.0
E2-10
Motor
iron loss for
torque
compensation
W
2850
3200
3700
4700
L2-02
Momentary
power loss
ridethru
time
s
2.0
2.0
2.0
2.0
L2-03
Min.
baseblock (BB)
time
s
1.8
1.9
2.0
2.1
L2-04
Voltage
recovery time
s
1.0
1.0
1.0
1.0
L8-02
Overheat
pre-alarm level
°
C
95
95
95
95