6 Basic Parameter Settings
6 - 50
High-function General-purpose Inverter RX2 Series User’s Manual
Reduced Torque Characteristics [bC111]=00
Can be used for load reduction in accordance with the cooling performance at a low speed.
(Ex.2) Induction motor rated current 64A, [bC110]=64 (A)
For base frequency [Hb104]=60 Hz, output frequency=20 Hz
When the first electronic thermal level [bC110] is 64 A, the reduction ratio is ×0.8 for operations at a
base frequency of 60 Hz and output frequency of 20 Hz and the electronic thermal time-limited char-
acteristics are given in the lower part of Example 2.
Since Example 1 shows the case of the reduction ratio ×1, a trip occurs in 60 seconds when an elec-
tric current of 150% ×1 of the motor rated current flows continuously. However in Example 2, a trip
occurs in 60 seconds when an electric current of 150%×0.8=120% of the motor rated current flows
continuously.
X1.0
5
16
50
X0.8
X0.6
0
6
20
60
0
Output frequency (Hz)
Base frequency
Reduction ratio
56.3
(88%))
76.8
(120%)
102.4
(160%)
0
60
3
×1
×0.8
Output current (A)
(Ratio to motor rated current)
Trip time (s)
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......