C - 25
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
AC-88
○
Deceleration time setting for
multi-speed 15
0.00 to 3600.00 (s)
0.00
AC215
-
Select method to switch to
Accel2/Decel2 Profile,
2nd-motor
00 ([2CH] terminal)/01 (Parameter setting)/
02 (Switching normal/reverse rotation)
00
AC216
○
Accel1 to Accel2 Frequency
transition point, 2nd-motor
0.00 to 590.00 (Hz)
0.00
AC217
○
Decel1 to Decel2 Frequency
transition point, 2nd-motor
0.00 to 590.00 (Hz)
0.00
AC220
○
Acceleration time setting 1,
2nd-motor
0.00 to 3600.00 (s)
30.00
AC222
○
Deceleration time setting 1,
2nd-motor
0.00 to 3600.00 (s)
30.00
AC224
○
Acceleration time setting 2,
2nd-motor
0.00 to 3600.00 (s)
15.00
AC226
○
Deceleration time setting 2,
2nd-motor
0.00 to 3600.00 (s)
15.00
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
Ad-01
-
Torque reference input source
selection
01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)/15 (PID calculation)
07
Ad-02
○
Torque reference value setting
-500.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of inverter ND rat-
ing)
0.0
Ad-03
-
Polarity selection for torque ref-
erence
00 (As per the sign)/
01 (Follow the revolution direction)
00
Ad-04
○
Switching time of Speed control
to Torque control
0 to 1000 (ms)
100
Ad-11
-
Torque bias input source selec-
tion
00 (Disabled)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)/15 (PID calculation)
00
Ad-12
○
Torque bias value setting
-500.0 to 500.0 (%)
(Limited at a torque equivalent to 200% of inverter ND rat-
ing)
0.0
Ad-13
-
Polarity selection for torque bias
00 (As per the sign)/
01 (Follow the revolution direction)
00
Ad-14
-
Terminal [TBS] active
00 (Disabled)/01 (Enabled)
00
Ad-40
-
Input selection for speed limit at
torque control
01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)
07
Ad-41
○
Speed limit at torque control (at
Forward rotation)
0.00 to 590.00 (Hz)
0.00
Ad-42
○
Speed limit at torque control (at
Reverse rotation)
0.00 to 590.00 (Hz)
0.00
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......