8 - 181
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
1 Ou
tpu
t T
ermin
al Fu
n
ction
8
8-1
1-5
Analog Output
Ter
mina
l Switch Setting
s
With Analog output terminals Ao1 and Ao2, you can select voltage output or current output by operating
Switches SW3 and SW4 on the substrate.
Precautions for Correct Use
• In the switch setting on the substrate during factory setting, [A01] is output voltage; [A02] is
output current.
• Operate the switches on the substrate while the inverter power supply is turned off.
• When [Cd-10]=01 is set, [FM], [Ao1], and [Ao2] respectively perform outputs in accordance
with values of [Cd-15], [Cd-25], and [Cd-35].
Parameter
8-11-5 Analog Output Terminal Switch Settings
Item
Parameter
Data
Description
Default
data
[Ao1] monitor output
selection
[Cd-04]
Parameter
number for
Sets a parameter number.
[dA-01]
[Ao2] monitor output
selection
[Cd-05]
[dA-01]
Analog monitor adjust
mode enable
[Cd-10]
00
Invalid.
00
01
Valid. Outputs to terminals output levels in
the adjustment mode.
Filter time constant of
[Ao1] monitor
[Cd-21]
1 to 500[ms]
Filters and outputs the selected data.
100
[Ao1] Data type
selection
[Cd-22]
00
Outputs the absolute value of data.
00
01
Outputs data with a symbol as is.
[Ao1] monitor bias
adjustment
[Cd-23]
-100.0 to
100.0[%]
Biases data to adjust Point 0 of data.
0.0
[Ao1] monitor gain
adjustment
[Cd-24]
-1000.0 to
1000.0[%]
Apply a gain to data to adjust an inclination
in data.
100.0
Output level setting at
[Ao1] monitor adjust
mode
[Cd-25]
-100.0 to
100.0[%]
Sets output in the adjustment mode. It
selects the maximum output (at 100.0%),
the minimum output (at 0.0%) ([Cd-22]=00),
or the minimum output (at -100.0%)
([Cd-22]=01).
100.0
Filter time constant of
[Ao2] monitor
[Cd-31]
1 to 500[ms]
Filters and outputs the selected data.
100
[Ao2] Data type
selection
[Cd-32]
00
Outputs the absolute value of data.
0
01
Outputs data with a symbol as is.
[Ao2] monitor bias
adjustment
[Cd-33]
-100.0 to
100.0[%]
Biases data to adjust Point 0 of data.
20.0
[Ao2] monitor gain
adjustment
[Cd-34]
-1000.0 to
1000.0[%]
Apply a gain to data to adjust an inclination
in data.
80.0
Output level setting at
[Ao2] monitor adjust
mode
[Cd-35]
-100.0 to
100.0[%]
Sets output in the adjustment mode. It
selects the maximum output (at 100.0%),
the minimum output (at 0.0%) ([Cd-32]=00),
or the minimum output (at -100.0%)
([Cd-32]=01).
100.0
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......