7 - 49
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
3 T
orqu
e Con
tro
l
7
7-3
-4
Tor
que Limit
Functio
n
Input Terminal Function [CA-01] to [CA-11]
Output Terminal [CC-01] to [CC-07]
(a) Analog input mode
It is a mode to set a torque limit value in all operation states by applied voltage/current by setting
the Ai1/Ai2/Ai3 terminal on the control terminal block in the torque limit selection [bA110].
In the case of setting torque bias, values corresponding to analog input are as follows.
• Input to Ai1/Ai2 Terminal
• Input to Ai3 Terminal
The setting of the ratio above can be changed by adjusting the analog input start end function.
See
(e.g.) In the case of setting 0.0 to 50.0% to the torque command addition value for 0-10 (V)/0-20
(mA) input as [Ai1], set 10.0% for [Cb-04] to make it 50.0% against maximum 500.0%.
([Cb-03]=0.0,[Cb-04]=10.0,[Cb-05]=0.0,[Cb-06]=100.0)
(b) 4 Quadrant specific setting mode
It is a mode to set respective torque limits 1 to 4 ([bA112] to [bA115]) in the four quadrants of normal
powered, normal regenerative, reverse powered, and reverse regenerative.
It will be enabled when torque limit selection [bA110] = 07 (parameter setting) and torque limit mode
selection [bA111] = 00 (by each quadrant).
The relationship of four quadrants and torque limits is shown in the figure below.
Item
Terminal name Data
Description
Validation of torque limit
[TL]
060
Switches enable/disable of the torque limit func-
tion.
Torque limit switchover 1
[TRQ1]
061
Is the torque limit command switch terminal 1.
Torque limit switchover 2
[TRQ2]
062
Is the torque limit command switch terminal 2.
Item
Terminal name Data
Description
During torque limitation
[TRQ]
022
Signal turns ON when the torque limit function is
enabled.
0 to 10 (V)/0 to 20 (mA) corresponding value
Torque command addition 0.0 to 500.0(%)
-10 to 10 (V) corresponding value
Torque command addition -500.0 to 500.0(%)
Torque
Powered
[bA112]
Regenerative
[bA113]
Reverse
Normal
Powered
[bA114]
Regenerative
[bA115]
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......