C - 63
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
Parameter Mode (Code o)
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
oA-10
○
Operation mode on option card error
(SLOT-1)
00 (Error)/01 (Continue operation)
00
oA-11
○
Communication Watch Dog Timer
0.00 to 100.00 (s)
1.00
oA-12
-
Action selection at communication error
00 (Error)/
01 (Trip after deceleration stop)/02 (Ignore)/
03 (Free run)/04 (Deceleration stop)
01
oA-13
-
Run command enable option during the
option card (SLOT-1) start-up
00 (Operation command disabled)/
01 (Operation command enabled)
00
oA-20
○
Operation mode on option card error
(SLOT-2)
00 (Error)/01 (Continue operation)
00
oA-21
○
Communication Watch Dog Timer
0.00 to 100.00 (s)
1.00
oA-22
-
Action selection at communication error
00 (Error)/
01 (Trip after deceleration stop)/02 (Ignore)/
03 (Free run)/04 (Deceleration stop)
01
oA-23
-
Run command enable option during the
option card (SLOT-2) start-up
00 (Operation command disabled)/
01 (Operation command enabled)
00
oA-30
○
Operation mode on option card error
(SLOT-3)
00 (Error)/01 (Continue operation)
00
oA-31
○
Communication Watch Dog Timer
0.00 to 100.00 (s)
1.00
oA-32
-
Action selection at communication error
00 (Error)/
01 (Trip after deceleration stop)/02 (Ignore)/
03 (Free run)/04 (Deceleration stop)
01
oA-33
-
Run command enable option during the
option card (SLOT-3) start-up
00 (Operation command disabled)/
01 (Operation command enabled)
00
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
ob-01
-
Encoder constant setting
32 to 65535 (pls)
1024
ob-02
-
Encoder position selection
00 (Phase-A is leading)/
01 (Phase-B is leading)
00
ob-03
-
Motor gear ratio numerator
1 to 10000
1
ob-04
-
Motor gear ratio denominator
1 to 10000
1
ob-10
-
Pulse train detection object selection
00 (Command)/
01 (Pulse string position command)
00
ob-11
-
Mode selection of pulse train input
00 (90° phase difference)/
01 (forward/reverse rotation command and rotation
direction)/
02 (forward/reverse rotation pulse string)
01
ob-12
○
Pulse train frequency Scale
0.05 to 200.0 (kHz)
25.00
ob-13
○
Pulse train frequency Filter time con-
stant
0.01 to 2.00 (s)
0.10
ob-14
○
Pulse train frequency Bias value
-100.0 to 100.0 (%)
0.0
ob-15
○
Pulse train frequency High Limit
0.0 to 100.0 (%)
100.0
ob-16
○
Pulse train frequency detection low
level
0.0 to 100.0 (%)
0.0
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......