C - 59
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
Hb162
-
Free-V/f frequency 7 setting,
1st-motor
[Hb160] to [Hb104] (Hz)
0.00
Hb163
-
Free-V/f Voltage 7 setting,
1st-motor
0.0 to 1000.0 (V)
0.0
Hb170
○
Slip Compensation P-gain with
encoder, 1st-motor
0 to 1000 (%)
100
Hb171
○
Slip Compensation I-gain with
encoder, 1st-motor
0 to 1000 (%)
100
Hb180
○
Output voltage gain, 1st-motor
0 to 255 (%)
100
Hb202
-
Async.Motor capacity setting,
2nd-motor
0.01 to 160.00 (kW)
*1
Hb203
-
Async.Motor poles setting,
2nd-motor
2 to 48 (poles)
4
Hb204
-
Async.Motor Base frequency
setting, 2nd-motor
10.00 to 590.00 (Hz)
50.00
*2
Hb205
-
Async.Motor Maximum fre-
quency setting, 2nd-motor
10.00 to 590.00 (Hz)
50.00
*2
Hb206
-
Async.Motor rated voltage,
2nd-motor
1 to 1000 (V)
200 V class: 230
400 V class: 400
*2
Hb208
-
Async.Motor rated current,
2nd-motor
0.01 to 10000.00 (A)
*1
Hb210
-
Async.Motor constant R1,
2nd-motor
0.000001 to 1000.000000 (Ω)
*1
Hb212
-
Async.Motor constant R2,
2nd-motor
0.000001 to 1000.000000 (Ω)
*1
Hb214
-
Async.Motor constant L,
2nd-motor
0.000001 to 1000.000000 (mH)
*1
Hb216
-
Async.Motor constant Io,
2nd-motor
0.01 to 10000.00 (A)
*1
Hb218
-
Async.Motor constant J,
2nd-motor
0.00001 to 10000.00000 (kgm
2
)
*1
Hb230
-
Minimum frequency adjust-
ment, 2nd-motor
0.10 to 10.00 (Hz)
0.50
Hb231
○
Reduced voltage start time set-
ting, 2nd-motor
0 to 2000 (ms)
36
Hb240
-
Manual torque boost opera-
tional mode selection,
2nd-motor
00 (Disabled)/
01 (Always enabled)/
02 (Enabled only for forward revolution)/
03 (Enabled only for reverse revolution)
01
Hb241
○
Manual torque boost value,
2nd-motor
0.0 to 20.0 (%)
0.0
Hb242
○
Manual torque boost Peak
speed, 2nd-motor
0.0 to 50.0 (%)
0.0
Hb245
-
Eco drive enable, 2nd-motor
00 (Disabled)/01 (Enabled)
00
Hb246
○
Eco drive response adjustment,
2nd-motor
0.0 to 100.0 (%)
50.0
Hb250
-
First free V/f frequency 2
0.00 to [Hb252] (Hz)
0
Hb251
-
Free-V/f Voltage 1 setting,
2nd-motor
0.0 to 1000.0 (V)
0.0
Hb252
-
Free-V/f frequency 2 setting,
2nd-motor
[Hb250] to [Hb254] (Hz)
0.00
Hb253
-
Free-V/f Voltage 2 setting,
2nd-motor
0.0 to 1000.0 (V)
0.0
Hb254
-
Free-V/f frequency 3 setting,
2nd-motor
[Hb252] to [Hb256] (Hz)
0.00
Hb255
-
Free-V/f Voltage 3 setting,
2nd-motor
0.0 to 1000.0 (V)
0.0
Hb256
-
Free-V/f frequency 4 setting,
2nd-motor
[Hb254] to [Hb258] (Hz)
0.00
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......