8 - 171
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-10
Inpu
t T
ermin
al Fu
n
ct
ion
8
8-1
0-7
Automatic R
eset
Functio
n
The following is an example of operation of automatic resetting.
(Ex.1) When [bb-10]=01
(Ex.2) When [bb-10]=02
*1. When [bb-11]=00, the error output becomes the “[AL] output.”
Parameter
Item
Parameter
Data
Description
Default
data
Automatic reset
selection
[bb-10]
00
Invalid
00
01
Resetting starts when the operation instruc-
tion is turned off.
02
Resetting starts after the set time has
elapsed.
Alarm signal selection
at Automatic error
reset is active
[bb-11]
00
Outputting is available.
00
01
Outputting is not available.
Automatic error reset
wait time
[bb-12]
0 to 600(s)
Sets a stand-by time from when resetting
starts to when actual resetting starts.
2
Automatic error reset
number
[bb-13]
0 to 10 (times)
Sets the number of automatic resetting.
3
[bb -12]
Output frequency
Restarting in accordance with [bb-41]
Operation
instruction [FW]
Error output
*1
[bb -12]
Output frequency
Restarting in accordance with [bb-41]
Operation
instruction [FW]
Error output
*1
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......