C - 39
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
bb-82
-
Speed deviation error mode
selection
00 (Warning)/01 (Error)
00
bb-83
-
Speed deviation error detection
level
0.0 to 100.0 (%)
15.0
bb-84
-
Speed deviation error detection
time
0.0 to 5.0 (s)
0.5
bb-85
-
Position deviation error mode
selection
00 (Warning)/01 (Error)
00
bb-86
-
Position deviation error detec-
tion level
0.0 to 65535 (×100pls)
4096
bb-87
-
Position deviation error detec-
tion time
0.0 to 5.0 (s)
0.5
bb201
○
Carrier speed setting,
2nd-motor
[Ub-03]=02: Normal duty
0.5 to 16.0 (kHz)
[Ub-03]=01: Low duty
0.5 to 12.0 (kHz)
[Ub-03]=00: Very low duty
0.5 to 10.0 (kHz)
*1
2.0
bb202
-
Sprinkle carrier pattern selec-
tion, 2nd-motor
00 (Disabled)/01 (Pattern 1 enabled)/
02 (Pattern 2 enabled)/03 (Pattern 3 enabled)/
00
bb203
○
Automatic-carrier reduction
selection, 2nd-motor
00 (Disabled)/01 (Enabled: current)/
02 (Enabled: temperature)
00
bb260
-
Over current detection level,
2nd-motor
(0.2 to 2.2)
x Inverter ND rated current (A)
*3
2.2
× Inverter
rated current
*1. 3G3RX2-B4750 to 3G3RX2-B413K shall be as follows.
[Ub-03]=02: 0.5 to 10.0 (kHz)
[Ub-03]=00 or 01: 0.5 to 8.0 (kHz)
*2. Feedback input to the followings is required:
• Input Terminal A and B
• Optional cassette RX2-PG
*3. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A,V). When the data of
[CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......