6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-1 B
asic Parame
ter Sett
ing
s
6
6-1-2 Invert
er Initia
lization
Table of Initialization Targets
[Ub-01] Selection of initialization:
Initialization targets are indicated by
.
Initialize Data selection [Ub-02]
The data is initialized in the following manners, depending on the selected mode. The default data is
common in other parameters.
Set the default data during shipment to 01 (Mode 1).
[Ub-01]
(1)
History data
(2)
Setting of I/O
terminal
(3)
Communica-
tion function
(4)
Other than
parameters (2)
and (3)
(5)
DriveProgram-
ming
00
01
02
03
04
05
06
07
08
Code
Function Name
Mode 0
Mode 1
(Default data
during shipment)
Mode 2
Mode 3
AA101 Main speed input source
selection, 1st-motor
07 (Parameter set-
ting)
01 (Ai1 terminal
input)
01 (Ai1 terminal
input)
01 (Ai1 terminal
input)
AA111
Run-command input source
selection, 1st-motor
02 (RUN key on
operator LCD
Operator)
00 ([FW]/[RV] ter-
minal)
00 ([FW]/[RV] ter-
minal)
00 ([FW]/[RV] ter-
minal)
AA201 Main speed input source
selection, 2nd-motor
07 (Parameter set-
ting)
01 (Ai1 terminal
input)
01 (Ai1 terminal
input)
01 (Ai1 terminal
input)
AA211
Run-command input source
selection, 2nd-motor
02 (RUN key on
operator LCD
Operator)
00 ([FW]/[RV] ter-
minal)
00 ([FW]/[RV] ter-
minal)
00 ([FW]/[RV] ter-
minal)
bC111
Electronic thermal charac-
teristic selection, 1st-motor
00 (Reduction
characteristics)
01 (Constant
torque characteris-
tics)
01 (Constant
torque characteris-
tics)
01 (Constant
torque characteris-
tics)
bC211
Electronic thermal charac-
teristic selection, 2nd-motor
00 (Reduction
characteristics)
01 (Constant
torque characteris-
tics)
01 (Constant
torque characteris-
tics)
01 (Constant
torque characteris-
tics)
Hb104
Async.Motor Base fre-
quency setting, 1st-motor
60.00
50.00
60.00
50.00
Hb105
Async.Motor Maximum fre-
quency setting, 1st-motor
60.00
50.00
60.00
50.00
Hb106
Async.Motor rated voltage,
1st-motor
200 V class: 200
400 V class: 400
200 V class: 230
400 V class: 400
200 V class: 230
400 V class: 460
200 V class: 230
400 V class: 400
Hb204
Async.Motor Base fre-
quency setting, 2nd-motor
60.00
50.00
60.00
50.00
Hb205
Async.Motor Maximum fre-
quency setting, 2nd-motor
60.00
50.00
60.00
50.00
Hb206
Async.Motor rated voltage,
2nd-motor
200 V class: 200
400 V class: 400
200 V class: 230
400 V class: 400
200 V class: 230
400 V class: 460
200 V class: 230
400 V class: 400
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......