8 Applied Settings
8 - 30
High-function General-purpose Inverter RX2 Series User’s Manual
Input Terminal Function
Data Monitor Function
Item
Terminal name
Data
Description
PID2 disable function
[PID2]
043
Disables the PID2 function by turning ON the termi-
nal function.
Frequency equivalent to the target value of PID2 will
be commanded when the terminal is turned ON.
PID2 I control integral
value clear
[PIDC2]
044
Clears the integral value of PID2 control.
PID3 disable function
[PID3]
045
Disables the PID3 function by turning ON the termi-
nal function.
Frequency equivalent to the target value of PID3 will
be commanded when the terminal is turned ON.
PID3 I control integral
value clear
[PIDC3]
046
Clears the integral value of PID3 control.
PID4 disable function
[PID4]
047
Disables the PID4 function by turning ON the termi-
nal function.
Frequency equivalent to the target value of PID4 will
be commanded when the terminal is turned ON.
PID4 I control integral
value clear
[PIDC4]
048
Clears the integral value of PID4 control.
PID output switch 1
[PIO1]
056
Switches PID output by a combination of PIO1 and
PIO2.
PID output switch 2
[PIO2]
057
Item
Parameter
Data
Description
PID2 target value
[FA-36]
-100.00 to 100.00(%)
*1
*1. Data range varies depending on the data from [AJ-04] to [AJ-06].
Displays the target value of PID2.
Changeable when [AJ-07] = 09.
PID2 feedback monitor
[db-36]
-100.00 to 100.00(%)
*1
Displays the feedback value of PID2.
PID2 output monitor
[db-55]
-100.00 to 100.00(%)
Displays the output value of PID2.
PID2 deviation monitor
[db-56]
-200.00 to 200.00(%)
Displays the deviation of PID2.
PID3 target value
[FA-38]
-100.00 to 100.00(%)
*2
*2. Data range varies depending on the data from [AJ-24] to [AJ-26].
Displays the target value of PID3.
Changeable when [AJ-27] = 09.
PID3 feedback monitor
[db-38]
-100.00 to 100.00(%)
*2
Displays the feedback value of PID3.
PID3 output monitor
[db-57]
-100.00 to 100.00(%)
Displays the output value of PID3.
PID3 deviation monitor
[db-58]
-200.00 to 200.00(%)
Displays the deviation of PID3.
PID4 target value
[FA-40]
-100.00 to 100.00(%)
*3
*3. Data range varies depending on the data from [AJ-44] to [AJ-46].
Displays the target value of PID4.
Changeable when [AJ-47] = 09.
PID4 feedback monitor
[db-40]
-100.00 to 100.00(%)
*3
Displays the feedback value of PID4.
PID4 output monitor
[db-59]
-100.00 to 100.00(%)
Displays the output value of PID4.
PID4 deviation monitor
[db-60]
-200.00 to 200.00(%)
Displays the deviation of PID4.
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......