2 Design
2 - 30
High-function General-purpose Inverter RX2 Series User’s Manual
Power Input/Output
(Wiring example)
When 24 V power is supplied to P+ and P- from an external source, change of parameters and commu-
nication of optional devices are enabled even without main power supply.
Terminal
symbol
Terminal
name
Description
Electrical characteristics
24V pow
er su
pply
Po
wer inp
ut
P24
24V output
power
terminal
24 VDC power supply for contact signal
The common terminal is P-.
100mA output at maximum
P+
External
24V input
terminal
(24V)
Input an external 24 VDC power to the
inverter. With input of 24 V power, you
can change parameter settings or oper-
ate optional communication without using
a control power supply
Allowable input voltage
24 VDC±10%
Maximum power consumption 1A
P-
Terminal
for P24/P+
(0 (zero) V)
P+
P24
P-
Control circuit terminal area
External
24V terminal
DC24V external power supply
DC24V external
power supply
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...