8 Applied Settings
8 - 10
High-function General-purpose Inverter RX2 Series User’s Manual
Input Terminal Function
Data Monitor Function
Item
Terminal name
Data
Description
PID disable function
[PID]
041
Disables the PID1 function by turning ON the terminal
function. When disabled, operation is done by using
the command set for target value as command fre-
quency.
PID1 I control inte-
gral value clear
[PIDC]
042
Clears integral value of PID1 control.
Multi-layer target
command terminal 1
[SVC1]
051
Switches multiple target values.
Multi-layer target
command terminal 2
[SVC2]
052
Multi-layer target
command terminal 3
[SVC3]
053
Multi-layer target
command terminal 4
[SVC4]
054
PID gain switch
[PRO]
055
Switches PID gain 1 and 2 by terminal.
Item
Parameter
Data
Description
PID1 target value 1
[FA-30]
0.00 to 100.00(%)
*1
*1. Data range varies depending on the data from [AH-04] to [AH-06].
Displays PID1 target value.
Is changeable when [AH-07] = 07 or
multi-layer target value 1-15 is enabled.
PID1 target value 2
[FA-32]
0.00 to 100.00(%)
*1
Displays PID1 target value 2.
Is changeable when [AH-42] = 07.
PID1 target value 3
[FA-34]
0.00 to 100.00(%)
*1
Displays PID1 target value 3.
Is changeable when [AH-46] = 07.
PID1 feedback data 1
monitor
[db-30]
-100.00 to 100.00(%)
*1
Displays PID1 feedback value 1.
PID1 feedback data 2
monitor
[db-32]
-100.00 to 100.00(%)
*1
Displays PID1 feedback value 2.
PID1 feedback data 3
monitor
[db-34]
-100.00 to 100.00(%)
*1
Displays PID1 feedback value 3.
PID1 target value monitor
after calculation
[db-42]
-100.00 to 100.00(%)
*1
Displays target value after calculation by
[AH-50].
PID1 feedback data
[db-44]
-100.00 to 100.00(%)
*1
Displays feedback value after calculation
by [AH-54].
PID1 output monitor
[db-50]
-100.00 to 100.00(%)
Displays PID1 output value.
PID1 deviation monitor
[db-51]
-200.00 to 200.00(%)
Displays PID1 deviation.
PID1 deviation 1 monitor
[db-52]
-200.00 to 200.00(%)
Monitors 3 deviations of PID1 when
[AH-50] = 05 or 06.
PID1 deviation 2 monitor
[db-53]
-200.00 to 200.00(%)
PID1 deviation 3 monitor
[db-54]
-200.00 to 200.00(%)
PID current P gain monitor
[db-61]
0.0 to 100.0
Displays current P gain.
PID current I gain monitor
[db-62]
0.0 to 3600.0(s)
Displays current I gain.
PID current D gain monitor
[db-63]
0.00 to 100.00(s)
Displays current D gain.
PID feed-forward monitor
[db-64]
-100.00 to 100.00(%)
Displays feed-forward command value.
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......