9 Communications Functions
9 - 68
High-function General-purpose Inverter RX2 Series User’s Manual
334Ah
3349h
Selection of restart mode
@over-voltage
bb-30
R/W
00: 0Hz
01: Frequency matching
02: Frequency entrainment
03: Detection speed
04: Trip after frequency matching
deceleration stop
-
334Bh
334Ah
Wait time of restart
@over-voltage
bb-31
R/W
0.3 to 100.0 (s)
0.1(s)
3354h
3353h
Restart mode after FRS
release
bb-40
R/W
00: 0Hz
01: Frequency matching
02: Frequency entrainment
03: Detection speed
*4
-
3355h
3354h
Restart mode after RS
release
bb-41
R/W
00: 0Hz
01: Frequency matching
02: Frequency entrainment
03: Detection speed
*4
3356h
3355h
Restart frequency threshold
bb-42
R/W
0 to 59000
0.01(Hz)
3357h
3356h
Restart level of Active fre-
quency matching
bb-43
R/W
(0.0 to 2.0)
× Inverter rated current
*1
0.1(A)
3358h
3357h
Restart constant(speed) of
Active frequency matching
bb-44
R/W
10 to 3000
0.01(s)
3359h
3358h
Restart constant(Voltage) of
Active frequency matching
bb-45
R/W
10 to 3000
0.01(s)
335Ah
3359h
OC-supress level of Active
frequency matching
bb-46
R/W
(0.0 to 2.0)
× Inverter rated current
*1
0.1(A)
335Bh
335Ah
Restart speed selection of
Active frequency matching
bb-47
R/W
00: Cutoff frequency
01: Maximum frequency
02: Setting frequency
-
3368h
3367h
Over current detection level,
1st-motor
bb160
R/W
(0.2 to 2.2)
x Inverter ND rated current
*1
0.1(A)
3369h
3368h
Power supply over voltage
selection
bb-61
R/W
00: Warning
01: Error
-
336Ah
3369h
Power supply over voltage
level setting
bb-62
R/W
(200V class) 3000 - 4100
(400V class) 6000 - 8200
0.1(Vdc)
336Ch
336Bh
Ground fault selection
bb-64
R/W
00: Disabled
01: Enabled
-
336Dh
336Ch
Input phase loss enable
bb-65
R/W
00: Disabled
01: Enabled
-
336Eh
336Dh
Output phase loss enable
bb-66
R/W
00: Disabled
01: Enabled
-
336Fh
336Eh
Output phase loss detection
sensitivity
bb-67
R/W
1 to 100
1(%)
3372h
3371h
Thermistor error level
bb-70
R/W
0 to 10000
1(Ω)
337Ch
377Bh
Over speed detection level
bb-80
R/W
0 to 1500
0.1(%)
337Dh
337Ch
Over speed detection time
bb-81
R/W
0 to 50
0.1(s)
337Eh
337Dh
Speed deviation error mode
selection
bb-82
R/W
00: Warning
01: Error
-
337Fh
337Eh
Speed deviation error detec-
tion level
bb-83
R/W
0 to 1000
0.1(%)
3380h
337Fh
Speed deviation error detec-
tion time
bb-84
R/W
0 to 50
0.1(s)
3381h
3380h
Position deviation error mode
selection
bb-85
R/W
00: Warning
01: Error
-
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W
Monitor or setting data
Resolution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......