6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-
2 Paramet
er Sett
ing f
o
r Mo
tor R
elated
6
6-
2-3
A
uto-tu
ning o
f Motor
1
Perform the offline auto-tuning.
The online auto-tuning works with the designated motor constants and the offline auto-tuning
described above is performed.
2
The Online auto-tuning selection [HA-03] is set.
Set the Online auto-tuning selection [HA-03] to 01: Enabled.
3
Check the online auto-tuning.
The online tuning operates for up to 5 s when every operation stops. Use the online tuning after
making sure that the operation and stop can be made correctly by your operation command.
Precautions for Correct Use
• In case of termination due to trip or erroneous tuning, correct data cannot be acquired. See
the following table.
• The result of the online tuning is automatically reflected in up to 5 seconds after the stop. It is
not reflected if the operation is restarted during the tuning.
• In the factory setting, the offline auto-tuning can be started by the RUN Key on the LCD oper-
ator. It can be changed to a designated operation command by changing the operation com-
mand [HA-02] of the auto-tuning.
• When the following settings are enabled, the Online auto-tuning is not performed:
• DC braking force setting
• Servo ON [SON], Forcing [FOC]
• Brake Control 2
How to Reset Failures of Auto-tuning
Precautions for Correct Use
In case of failure of the auto-tuning, the motor constant data are not updated and the motor
works in the untuned state.
Online Auto-tuning
Expected causes
Examples of measures
The control type is not suitable for the motor.
Since the tuning type changes depending on the Con-
trol mode selection, 1st-motor [AA121], IM control or
SM/PMM control, set the type in accordance with the
motor.
The base frequency, motor rated voltage, or motor
rated current is not suitable for the motor specifications.
Since wrong basic parameters of the motor could
cause excess current or trip, check the basic parame-
ters and set them appropriately.
STOP key was pressed.
Pressing the STOP key on the LCD operator interrupts
the auto-tuning. Check the setting of the auto-tuning
again before starting the tuning.
External factors such as braking caused a trip.
Factors that cause the trip need to be removed.
The input terminal function worked.
The tuning could be disturbed if the input terminal func-
tion works during the auto-tuning.
The motor capacity is too small compared to the one
set for the inverter.
If the tuning does not finish correctly, the motor con-
stants need to be set manually.
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......