8 Applied Settings
8 - 180
High-function General-purpose Inverter RX2 Series User’s Manual
db-44
PID1 feedback data monitor
-100.00 to 100.00(%)
*1
Outputting is possible with (±).
db-50
PID1 output monitor
-100.00 to 100.00(%)
Outputting is possible with (±).
db-51
PID1 deviation monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-52
PID1 deviation 1 monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-53
PID1 deviation 2 monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-54
PID1 deviation 3 monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-55
PID2 output monitor
-100.00 to 100.00(%)
Outputting is possible with (±).
db-56
PID2 deviation monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-57
PID3 output monitor
-100.00 to 100.00(%)
Outputting is possible with (±).
db-58
PID3 deviation monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-59
PID4 output monitor
-100.00 to 100.00(%)
Outputting is possible with (±).
db-60
PID4 deviation monitor
-200.00 to 200.00(%)
Outputting is possible with (±).
db-64
PID feedforward monitor
0.00 to 100.00(%)
dC-15
Cooling fin temperature monitor -20.0 to 200.0(°C)
*1. Data range varies depending on the data from [AH-04] to [AH-06].
*2. Data range varies depending on the data from [AJ-04] to [AJ-06].
*3. Data range varies depending on the data from [AJ-24] to [AJ-26].
*4. Data range varies depending on the data from [AJ-44] to [AJ-46].
Code
Name
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA / 0 to 100%)
Remarks
FA-01
Main speed command monitor
0.00 to 590.00(Hz)
FA-02
Auxiliary speed command mon-
itor
0.00 to 590.00(Hz)
FA-15
Torque command monitor
Motor rated torque ×
(-500.0 to 500.0(%))
*1
*1. To calculate the motor rated torque (100%), use the following formula.
Motor rated torque = 79.58 × Motor capacity × Number of poles/Base frequency
Example: Motor rated torque = 79.58 × 5.5 (kW) × 4 (P)/50 (Hz) ≈ 35 Nm
Outputting is possible with (±).
FA-16
Torque bias command monitor
Motor rated torque ×
(-500.0 to 500.0(%))
*1
Outputting is possible with (±).
FA-30
PID1 target value 1
0.00 to 100.00(%)
*2
*2. Data range varies depending on the data from [AH-04] to [AH-06].
FA-32
PID1 target value 2
0.00 to 100.00(%)
*2
FA-34
PID1 target value 3
0.00 to 100.00(%)
*2
FA-36
PID2 target value
0.00 to 100.00(%)
*3
*3. Data range varies depending on the data from [AJ-04] to [AJ-06].
FA-38
PID3 target value
0.00 to 100.00(%)
*4
*4. Data range varies depending on the data from [AJ-24] to [AJ-26].
FA-40
PID4 target value
0.00 to 100.00(%)
*5
*5. Data range varies depending on the data from [AJ-44] to [AJ-46].
Code
Name
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA / 0 to 100%)
Remarks
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......