8 Applied Settings
8 - 190
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.) Digital-frequency-outputting information on [dA-02] output current monitor
When a current equivalent to inverter rated current flows, provide output at 1,500 Hz.
Set [Cd-02]=3000Hz.
[Cd-13]=0.0%, [Cd-14]=100.0%
Set [Cd-02]=1500Hz.
[Cd-13]=0.0%, [Cd-14]=200.0%
Setting the analog monitor adjustment mode [Cd-10] to 01 fixes the output of the [FM] output terminal.
With the fixed output, an output set with [Cd-12] is made for the full-scale value of the monitor selected
with [Cd-03].
(Ex.) Outputting the output current monitor with the PWM output
When a current equivalent to inverter rated current flows, provide output with a PWM output at 100%.
(The standard point is the inverter rated current.)
1
Set [Cd-01]=00 and [Cd-03]=(dA-02).
Setting [Cd-10] to 01 outputs PWM from the [FM] terminal in accordance with [Cd-12].
Analog Monitor Adjustment Mode: [FM] Output
Code
Name
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA)
dA-02
Output current monitor
(0.00 to 2.00) ×
Inverter rated current (A)
3000
0
0A
1500
Rated current × 2 (A)
Output current (A)
Rated current
(A)
Digital frequency (Hz)
1500
0
0A
750
[Cd -14]=200.0%
Rated current × 2 (A)
Output current (A)
Rated current
(A)
Digital frequency (Hz)
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......