9 Communications Functions
9 - 66
High-function General-purpose Inverter RX2 Series User’s Manual
32Ech
32EBh
Decel-stop at power failure
freq. width at deceleration
start
bA-36
R/W
0 to 1000
0.01(Hz)
32Edh
32ECh
Decel-stop at power failure
DC-bus voltage constant con-
trol P-gain
bA-37
R/W
0 to 500
0.01
32Eeh
32EDh
Decel-stop at power failure
DC-bus voltage constant con-
trol I-gain
bA-38
R/W
0 to 15000
0.01(s)
32F0h
32EFh
Over-voltage suppression
enable, 1st-motor
bA140
R/W
00: Disabled
01: DC voltage constant deceler-
ation
02: Acceleration only at decelera-
tion
03: Acceleration at constant
speed/deceleration
-
32F1h
32F0h
Over-voltage suppression
active level, 1st-motor
bA141
R/W
(200Vclass) 3300 to 4000
(400Vclass) 6600 to 8000
0.1(Vdc)
32F2h
32F1h
Over-voltage suppression
action time, 1st-motor
bA142
(HIGH)
R/W
0 to 360000
0.01(s)
32F3h
32F2h
bA143
(LOW)
R/W
32F4h
32F3h
DC bus constant control pro-
portional gain, 1st-motor
bA144
R/W
0 to 500
0.01
32F5h
32F4h
DC bus constant control inte-
gral gain, 1st-motor
bA145
R/W
0 to 15000
0.01(s)
32F6h
32F5h
Over magnetization decelera-
tion function selection,
1st_motor
bA146
R/W
00: Disabled
01: Regular operation
02: Operation only at decelera-
tion
03: Level mode
04: Level mode only at decelera-
tion
-
32F7h
32F6h
Over magnetization output fil-
ter time constant, 1st_motor
bA147
R/W
0 to 100
0.01(s)
32F8h
32F7h
Over magnetization voltage
gain, 1st_motor
bA148
R/W
50 to 400
1(%)
32F9h
32F8h
Over magnetization level set-
ting, 1st_motor
bA149
R/W
(200V class) 3300 - 4000
(400V class) 6600 - 8000
0.1(Vdc)
3304h
3303h
Dynamic brake usage rate
bA-60
R/W
0.0 - 10.0×([bA-63]/minimum
resistance)
2*2
0.1(%)
3305h
3304h
Dynamic brake selection
bA-61
R/W
00: Disabled
01: Enabled: disabled at stop
02: Enabled: enabled at stop
-
3306h
3305h
Dynamic brake active level
bA-62
R/W
(200V class) 3300 - 4000
(400V class) 6600 - 8000
0.1(Vdc)
3307h
3306h
Dynamic brake resister value
bA-63
R/W
Minimum resistance - 600
*2
0.1(Ω)
330Eh
330Dh
Cooling FAN control method
selection
bA-70
R/W
00: Always ON
01: ON during operation
02: Temperature dependent
-
330Fh
330Eh
Cooling FAN accumulation
running time clear selection
bA-71
R/W
00: Disabled
01: Clear
-
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W
Monitor or setting data
Resolution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......