8 - 21
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
P
ID Con
trol
8
8-1
-4 PID Sleep F
unction
In the case of using this function, set 01 (output low) or 02 (SLEP terminal) to PID sleep condition
selection [AH-85].
You can change the start/cancel time and level of the sleep operation depending on the usage.
You can choose cancellation of the PID sleep status from 01 (deviation amount), 02 (feedback low),
and 03 (WAKE terminal) of the PID wake condition selection [AH-93].
In the case of canceling the PID sleep status by deviation, cancellation will only be activated when devi-
ation increases in a direction of lower output, even if PID1 deviation [AH-02] was set to 01 and PID
deviation ± was switched.
Parameter
8-1-4
PID Sleep Function
Item
Parameter
Data
Description
Default
data
PID sleep trigger
selection
[AH-85]
00
Disable
00
01
Starts sleep operation when output is low
02
Starts operation at the rising edge of the
[SLEP] terminal
PID sleep start level
[AH-86]
0.00 to
590.00(Hz)
Is a level of making a judgment of sleep
operation for the output speed when [AH-85]
= 01.
0.00
PID sleep active time
[AH-87]
0.00 to
100.00(s)
Is stand-by time before shifting to sleep
operation.
0.00
Setpoint boost before
PID sleep enable
[AH-88]
00
Disable
00
01
Boosts target value before sleep operation.
Setpoint boost time
[AH-89]
0.00 to
100.00(s)
Is actuation time prior to PID sleep.
0.00
Setpoint boost value
[AH-90]
0.00 to
100.00(%)
Sets a boost amount to be added to target
value before sleep.
0.00
Minimum RUN time
befor PID sleep
[AH-91]
0.00 to
100.00(s)
Does not start sleep operation until [AH-91]
has elapsed from start.
0.00
Minimum active time of
PID sleep
[AH-92]
0.00 to
100.00(s)
Retains the sleep status until [AH-92] has
elapsed, once the sleep operation started.
0.00
PID sleep trigger
selection
[AH-93]
01
Cancels the sleep operation when a devia-
tion amount increases in a deceleration
direction.
01
02
Cancels the sleep operation when feedback
value decreases.
03
Cancels the operation at the rising edge of
the [WAKE] terminal
PID wake start level
[AH-94]
0.00 to
100.00(%)
Cancels the operation when feedback value
goes below the set value when [AH-93] is
02.
0.00
PID wake start time
[AH-95]
0.00 to
100.00(s)
Is stand-by time for operation cancellation
when [AH-93] is 02.
0.00
PID wake start devia-
tion value
[AH-96]
0.00 to
100.00(%)
Cancels the operation when a deviation
between target value and feedback value
increases when [AH-93] is 01.
0.00
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......