11
Safety Precautions
High-function General-purpose Inverter RX2 Series User’s Manual
Be sure to confirm safety before conducting maintenance, inspection or parts
replacement.
Do not connect resistors to the terminals (PD/+1, P/+, N/-) directly. Doing so
might result in a small-scale fire, heat generation, or damage to the unit.
Install a stop motion device to ensure safety. Not doing so might result in a
minor injury.
(A holding brake is not a stop motion device designed to ensure safety.)
Be sure to use a specified type of braking resistor/regenerative braking unit.
In case of a braking resistor, install a thermal relay that monitors the tem-
perature of the resistor. Not doing so might result in a moderate burn due to
the heat generated in the braking resistor/regenerative braking unit. Config-
ure a sequence that enables the inverter power to turn off when unusual over
eating is detected in the braking resistor/regenerative braking unit.
The inverter has high voltage parts inside which, if short-circuited, might
cause damage to itself or other property. Place covers on the openings or
take other precautions to make sure that no metal objects such as cutting
bits or lead wire scraps go inside when installing and wiring.
Take safety precautions such as setting up a molded-case circuit breaker
(MCCB) that matches the inverter capacity on the power supply side.
Not doing so might result in damage to property due to the short circuit of the
load.
Do not dismantle, repair or modify the product.
Doing so may result in an injury.
If a parameter is set incorrectly when starting up, adjusting, maintaining, or
replacing, an unexpected operation may occur.
If the DriveProgramming stops during multi-function output, the output status
is held. Take safety precautions such as stopping peripheral devices.
Place covers on the openings or take other precautions to make sure that no
metal objects such as cutting bits or lead wire scraps go inside when install-
ing the PG Unit and wiring.
Caution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......