9 Communications Functions
9 - 96
High-function General-purpose Inverter RX2 Series User’s Manual
3E8Dh
3E8Ch
run command enable option
during the option card
(SLOT-1) start-up
oA-13
R/W
00: Operation command disabled
01: Operation command enabled
-
3E94h
3E93h
Operation mode on option
card error (SLOT-2)
oA-20
R/W
00: Error
01: Continue operation
-
3E95h
3E94h
Communication Watch Dog
Timer
oA-21
R/W
0 to 10000
0.01(s)
3E96h
3E95h
Action selection at communi-
cation error
oA-22
R/W
00: Error
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration stop
-
3E97h
3E96h
run command enable option
during the option card
(SLOT-2) start-up
oA-23
R/W
00 (Operation command dis-
abled)/
01 (Operation command enabled)
-
3E9Eh
3E9Dh
Operation mode on option
card error (SLOT-3)
oA-30
R/W
00: Error
01: Continue operation
-
3E9Fh
3E9Eh
Communication Watch Dog
Timer
oA-31
R/W
0 to 10000
0.01(s)
3EA0h
3E9Fh
Action selection at communi-
cation error
oA-32
R/W
00: Error
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration stop
-
3EA1h
3EA0h
run command enable option
during the option card
(SLOT-3) start-up
oA-33
R/W
00: Operation command disabled
01: Operation command enabled
-
3EE5h
3EE4h
Encoder constant setting
ob-01
R/W
32 to 65535
1(pls)
3EE6h
3EE5h
Encoder position selection
ob-02
R/W
00: Phase-A is leading
01: Phase-B is leading
-
3EE7h
3EE6h
Motor gear ratio Numerator
ob-03
R/W
1 to 10000
1
3EE8h
3EE7h
Motor gear ratio Denominator
ob-04
R/W
1 to 10000
1
3EEEh
3EEDh
Pulse train detection object
selection
ob-10
R/W
00: Command
01: Pulse string position com-
mand
-
3EEFh
3EEEh
Mode selection of pulse train
input
ob-11
R/W
00: 90° phase difference
01: forward/reverse rotation com-
mand and rotation direction
02: forward/reverse rotation pulse
string
-
3EF0h
3EEFh
Pulse train frequency Scale
ob-12
R/W
5 to 20000
0.01
(kHz)
3EF1h
3EF0h
Pulse train frequency Filter
time constant
ob-13
R/W
1 to 200
0.01(s)
3EF2h
3EF1h
Pulse train frequency Bias
value
ob-14
R/W
-1000 to 1000
0.1(%)
3EF3h
3EF2h
Pulse train frequency High
Limit
ob-15
R/W
0 to 1000
0.1(%)
3EF4h
3EF3h
Pulse train frequency detec-
tion low level
ob-16
R/W
0 to 1000
0.1(%)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......