8 Applied Settings
8 - 8
High-function General-purpose Inverter RX2 Series User’s Manual
Parameter
Item
Parameter
Data
Description
Default
data
PID1 enable
[AH-01]
00
Disable
00
01
Enable (if command becomes negative, it does
not output in a reverse direction)
02
Enable (if command becomes negative, it out-
puts in a reverse direction)
PID1 deviation inverse
[AH-02]
00
Disable
00
01
Enable (polarity inversion of deviation)
PID1 deviation inverse
[AH-07]
00 to 13
00: Disable, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved), 05: (Reserved),
06: (Reserved), 07: Parameter setting [AH-10]
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option)
07
Set-point-1 setting for
PID1
[AH-10]
-100.00 to
100.00(%)
*1
*1. Data range varies depending on the data from [AH-04] to [AH-06].
This is a set value 1 of PID1 target value 1.
0.00
Input source selection
of Set-point 2 for PID1
[AH-42]
00 to 13
00: Invalid, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved), 05: (Reserved),
06: (Reserved), 07: Parameter setting [AH-44],
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option)
00
Set-point 2 setting for
PID1
[AH-44]
-100.00 to
100.00(%)
*1
This is a set value of PID1 target value 2.
0.00
Input source selection
of Set-point 3 for PID1
[AH-46]
00 to 13
00: Invalid, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved), 05: (Reserved),
06: (Reserved), 07: Parameter setting [AH-48],
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option)
00
Set-point 3 setting for
PID1
[AH-48]
-100.00 to
100.00(%)
*1
This is a set value of PID1 target value 3.
0.00
Calculation symbol
selection of Set-point 1
for PID1
[AH-50]
01
(Target value 1) + (Target value 2)
01
02
(Target value 1) - (Target value 2)
03
(Target value 1) x (Target value 2)
04
(Target value 1) / (Target value 2)
05
Minimum deviation among input destinations 1,
2, and 3
06
Maximum deviation among input destinations 1,
2, and 3
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......