8 - 179
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
1 Ou
tpu
t T
ermin
al Fu
n
ction
8
8-1
1-4
Analog Output
Ter
mina
l Adjustment
Precautions for Correct Use
Data with (±) will be applied to [FM], [Ao1], and [Ao2] when [Cd-12], [Cd-22], and [Cd-32] are
01, respectively. If [Cd-12], [Cd-22], and [Cd-32] are 00, respectively, data with (−) is output as
the absolute value with (+).
dA-18
Output voltage monitor
0 to Rated voltage × 133% (V)
dA-30
Input power monitor
0.00 to Rated power ×
200% (kW)
dA-34
Output power monitor
0.00 to Rated power ×
200% (kW)
Outputting is possible with (±).
Outputting with (+) at powered
state and with (−) at
regenerative state.
dA-38
Motor temperature monitor
-20.0 to 200.0(°C)
dA-40
DC voltage monitor
(200 V class)
0.0 to 400.0 (Vdc)
(400 V class)
0.0 to 800.0 (Vdc)
dA-41
Braking circuit (BRD) duty ratio
monitor
0.00 to 100.00(%)
dA-42
Electronic thermal duty ratio
monitor (motor)
0.00 to 100.00(%)
dA-43
Electronic thermal duty ratio
monitor (inverter)
0.00 to 100.00(%)
dA-61
Analog input [Ai1] monitor
0.00 to 100.00(%)
dA-62
Analog input [Ai2] monitor
0.00 to 100.00(%)
dA-63
Analog input [Ai3] monitor
-100.00 to 100.00(%)
Outputting is possible with (±).
dA-70
Pulse string input monitor
(main body)
-100.00 to 100.00(%)
Outputting is possible with (±).
dA-71
Pulse string input monitor
(option)
-100.00 to 100.00(%)
Outputting is possible with (±).
*1. To calculate the motor rated torque (100%), use the following formula.
Motor rated torque = 79.58 × Motor capacity × Number of poles/Base frequency
Example: Motor rated torque = 79.58 × 5.5 (kW) × 4 (P)/50 (Hz) ≈ 35 Nm
Code
Name
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA / 0 to 100%)
Remarks
db-18
Analog output monitor YA1
0.00 to 10000
db-19
Analog output monitor YA2
0.00 to 10000
db-20
Analog output monitor YA3
0.00 to 10000
db-21
Analog output monitor YA4
0.00 to 10000
db-22
Analog output monitor YA5
0.00 to 10000
db-23
Analog output monitor YA6
0.00 to 10000
db-30
PID1 feedback data 1 monitor
-100.00 to 100.00(%)
*1
Outputting is possible with (±).
db-32
PID1 feedback data 2 monitor
-100.00 to 100.00(%)
*1
Outputting is possible with (±).
db-34
PID1 feedback data 3 monitor
-100.00 to 100.00(%)
*1
Outputting is possible with (±).
db-36
PID2 feedback data monitor
-100.00 to 100.00(%)
*2
Outputting is possible with (±).
db-38
PID3 feedback data monitor
-100.00 to 100.00(%)
*3
Outputting is possible with (±).
db-40
PID4 feedback data monitor
-100.00 to 100.00(%)
*4
Outputting is possible with (±).
db-42
PID1 target value monitor
-100.00 to 100.00(%)
*1
Outputting is possible with (±).
Code
Name
Output scale range
(Corresponding to 0 to 10 V /
0 to 20 mA / 0 to 100%)
Remarks
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......