High-function General-purpose Inverter RX2 Series User’s Manual
2-3 W
irin
g
2
2-
3-4 Wiring for
Main C
ir
cuit
Ter
mina
ls
To prevent electric shock, be sure to ground the inverter and the motor.
The 200-V class should be connected to the ground terminal under type-D grounding conditions (con-
ventional Class 3 grounding conditions: 100 Ω or less ground resistance). The 400-V class should be
connected to the ground terminal under type-C grounding conditions (conventional special Class 3
grounding conditions: 10 Ω or less ground resistance).
For the ground cable, use the applicable cable or a cable with a larger diameter. Make the cable length
as short as possible.
When several inverters are connected, the ground cable must not be connected across several invert-
ers or looped. Otherwise, the inverters and peripheral control equipment may malfunction.
In recent years, there is an increasing concern about suppressing the harmonic currents to the power
supply line in accordance with “Guideline to reduce harmonic emissions caused by electrical and elec-
tronic equipment for household and general use.”
The following provides an overview of harmonics and measures against harmonics implemented in this
inverter.
Harmonics
The voltage or current whose frequency is an
integral multiple of certain standard frequency
(base frequency) is called a harmonic.
If a commercial power supply frequency of 60 Hz
(50 Hz) is the reference frequency, the harmonics
of that signal is:
x2 = 120 Hz (100 Hz),
x3 = 180 Hz (150 Hz), and so on.
Reason Why Harmonics Cause Prob-
lems
As the number of harmonics increases, the wave-
form of the commercial supply has more distor-
tion. This distortion causes the malfunction of the
connected equipment or leads to abnormal heat
generation.
Wiring for Ground Terminal (G
)
Harmonic Current Measures and DC/AC Reactor Wiring (PD, P)
Inverter
Your ground
bolt
Inverter
Inverter
Inverter
Inverter
Inverter
Base frequency
(60 Hz)
2nd harmonics (120 Hz)
3rd harmonics (180 Hz)
3rd harmonics (180 Hz)
Base frequency (60 Hz)
Distorted waveform
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......